6. Commissioning, operation
Electrical connection
The instruments are designed to operate with safety extra-low voltage
(SELV). When wiring up the instruments, the technical specifications
for those instruments should be followed. In the case of a sensor with
GB
transmitter, as a rule, the transmitter should be operated in the middle
of the measuring range, since deviations can occur at the range limits.
The ambient temperature of the transmitter electronics should be kept
constant.
The transmitters must be operated at a constant operating voltage
(±0.2 V). Current/voltage spikes from switching the power supply on or
off must be prevented by the customer.

Connection diagram

Output 0 ... 10 V / 4 ... 20 mA (temperature)
Connection diagram
see commissioning of the option with relay
10
Output 0 ... 10 V / 4 ... 20 mA (air velocity)
Supply voltage
Jumper for the setting of the outputs (mA/V)
Both outputs can be set independently
Jumper measuring range
WIKA operating instructions air2guide model A2G-20
Temperature 4 ... 20 mA air
velocity 4 ... 20 mA
Temperature 0 ... 10 V air velocity
0 ... 10 V
Jumper:
Measuring range:
2 m/s
10 m/s
20 m/s