Bosch FPC-500 Serie Guía De Instalación Rápida página 36

Ocultar thumbs Ver también para FPC-500 Serie:
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 47
36
en | Installation
1.7.1
Inputs
1.7.2
Zones
Figure 1.1:
Notice!
i
Do not connect the zone- with any power+ like for example: AUX power, external power
supply or batteries for emergency power supply.
If EOL modules are used, the system is in line with VdS 2540 (detecting creeping short /
creeping open).
Notice!
i
Note that the maximum line resistance for conventional zones is 22.5 ohm.
The voltage of the zones is 20 VDC ±1 V.
The maximum current of the zones is 100 mA ±5 mA.
Notice!
i
Observe local regulations for the maximum number of detectors in a zone.
2022.03 | 10 | F.01U.172.981
1 Inputs
2 Zones
3 Aux power supply
4 Notification appliances
5 Alarm and fault relay
820Ω ± 5%
b+
a-
3,9kΩ
Quick installation guide
Conventional fire panel
b+
a-
EOL
Bosch Sicherheitssysteme GmbH
EOL
loading

Este manual también es adecuado para:

Fpc-500-2Fpc-500-4Fpc-500-8