6. Some fundamental rules which apply to all electrical devices
must be observed when using the heater:
• Do not touch the heather with wet hands.
• Do not handle with bare feet.
• Do not let children play with the electrical appliance.
7. Do not apply any modification to the product.
8. Keep connections dry.
9. If the power supply cord is damaged, avoid to use the appliance.
For power cord replacing, please contact the manufacturer or the
technical service or a person with similar qualification, in order to
avoid any risk.
10. If the appliance is not used for a long period, disconnect it from
the power supply.
Do not use it in small rooms used by people who are unable to
leave such rooms on their own unless they are under constant
surveillance or unless the product is in the version with the suffix
ED. In this case the heating appliance does feature an external
device to control ambient temperature.
All users should be made aware of all aspects of operation and
safety and these instructions should be retained for reference.
ELECTRICAL INSTALLATION
Before connecting the appliance make sure that the voltage
is the same as indicated on the device and the line supply is
corresponding to the effective rules.
The installation should always be carried out by a qualified electrician
or a competent person in accordance with the current electrical
standards for your country:
(ex. HD 384 CENELEC for Mainland Europe, IEC 60446 and BS 7671
for the United Kingdom, IEC 60445(2010) & ET101:2008 for Ireland
and IEC 60364-7 1988 Internationally, AS/NZS 3000 for Australia) and
according to the UE 2015/1188 standards.
The energy supply to the heater must always be properly earthed.
The appliance must be connected to energy supply line by means of
a not provided H05SS-F silicone cable.
An overvoltage category III Combined Circuit breaker and Residual
Current Device (RCD) with rated earth leakage operation not exceeding
30mA must be fitted upstream on the supply line in order to have a
contact separation in all poles that provide a full disconnection. The
circuit breaker must have a contact opening distance of at least 3
mm.
10