Setting Supplementary Electric Heater Setpoint; Setting Electric Heater Band In Supplementary/Replacement Mode; Setting Outside Air Temperature Threshold For Supplementary Mode; Setting Outside Air Temperature Threshold For Replacement Mode - AERMEC MODUCONTROL Manual De Instrucciones

Regulación eléctrica
Ocultar thumbs Ver también para MODUCONTROL:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

MIN
Index - String
value
0°C

Setting electric heater band in supplementary/replacement mode

MIN
Index - String
value
0°C

Setting outside air temperature threshold for supplementary mode

MIN
Index - String
value
-40°C

Setting outside air temperature threshold for replacement mode

MIN
Index - String
value
-40°C
MIN
Index - String
value
0°C
Parameters only visible in model set for
hot water production
Parameters only visible in models set for
hot domestic water production

Setting supplementary electric heater setpoint

MAX
value
This parameter indicates the deviation from the heating setpoint, for switching off the electric heater (if
65°C
active) in supplementary mode; as shown in Fig.12 on the previous page (Parameter Sri).
MAX
value
In supplementary mode, the temperature of the water in the system is checked before the unit is
switched on. If the temperature is less than/equal to the value calculated for the switch-on band, the
electric heater will be switched on and will operate as per the diagram on the previous page Fig.12.
20°C
The value of the switch-on band is calculated as follows: switch-on band = (Heating setpoint) -
(Parameter Sri) - (Parameter Bri); see Fig.12 on previous page;
In replacement mode, this parameter represents the band of deviation from the heating setpoint, within
which the heater will be activated or deactivated, as shown on the previous page Fig.13.
MAX
value
This parameter indicates the outside air temperature threshold, beneath which the heater is activated in
50°C
supplementary mode; as shown on the previous page, in Fig.11 Parameter tA1.
MAX
value
This parameter indicates the outside air temperature threshold, beneath which the heater is activated in
50°C
replacement mode; as shown on the previous page, in [Fig.A] Parameter tA2.

Setting the band for air temperature

MAX
value
20°C
This parameter indicates the band applied to the air temperature setpoints (tA1-tA2).
Parameter function
Parameter function
Parameter function
Parameter function
Parameter function
Parameters only visible in the models with DCP installed
Parameters only visible in bicompressor models
Parameters only visible in the models with inverter compressor
IMDCFJ. 12.05 6343841_03
67