ENGLISH
4.
CONTROL BOARD CONNECTION
Before attempting any work on the control board (connections, programming, maintenance), always turn off
power.
Important: High voltage could be present when disconnecting the J2 terminal board.
Observe points 10, 11, 12, 13 and 14 of the GENERAL SAFETY OBLIGATIONS.
Always separate power cables from control and safety cables (push-button, receiver, photocells, etc.). To prevent any
electric noise whatever, use separate sheaths.
For connections, refer to fig. 2 and 3
4.1
TERMINAL BOARD J1 (high voltage)
PE-N-L 230V~ 50Hz Power supply
Terminal board for power supply 230V~ 50Hz (L= Phase
N=Neutral). Connect the earth wire of the electric system and
the earth wire of the operator to the "PE" terminal.
4.2
TERMINAL BOARD J2 (high voltage)
11-12-13
Com-OP-CL = Motor
230V~ terminal board for connection of motor: connect motor
phases (Black and Brown wires) to the terminals 12 and 13,
connect the common (Blue wire) to the terminal 11. Connect the
thrust capacitor in parallel to the phases.
14-16
Courtesy lamp
230V~ terminal board for connection of courtesy lamp: connect
the courtesy lamp of the second up-and-over door or the
outside courtesy lamp with max power of 25W between terminals
14 and 16.
15-16
Flashing lamp
230V~ terminal board for connection of flashing lamp: connect
a flashing lamp with max. power of 40W between terminals 15
and 16.
4.3
TERMINAL BOARD J3 (low voltage)
1
Accessories supply input/Negative common.
2
Accessories supply input/Negative common.
3
Positive for powering 24 Vdc (+) accessories
Max. load of accessories: 300 mA.
To calculate absorption values, refer to the instructions for
individual accessories.
4
-FSW TX = Negative for power supply to photocell
transmitters.
Separate connection of the transmitters negative enables use of
Failsafe control on the photocells, thus increasing the system's
safety level.
5
FCA = Opening limit-switch contact (N.C.)
The opening limit-switch (optional) consists of a microswitch
which, when activated by the cam as the door reaches open
position, stops movement immediately.
Note: If limit-switch devices are not connected, jumper connect
"FCC" and "FCA" to the inputs Common.
6
FCC = Closing limit-switch contact (N.C.)
The closing limit-switch (optional) consists of a microswitch which,
when activated by the cam as the door reaches closed position,
performs a movement according to microswitches
programming.
Note: If limit-switch devices are not connected, jumper connect
"FCC" and "FCA" to the inputs Common.
PE N L
230 VAC
50 Hz
PE N L
230VAC
230V~
6
5
4
FSW
2
3
CL
1
2
1
5
4
FSW
2
3
OP
1
2
1
- -
+
1 2 3 4 5 6 7 8 9 10
J3
J2
J1
F1
1112 13 14 15 16
C
10µF
M
J2
J1
F1
11 12 13 14 15 16
M
50Hz
C
10µF
6
4
5
max
25W
M
C
10µF
BLINK
EXT. LAMP
Fig. 2
BLINK
Fig. 3