WARNING! Electric current!
Danger of electric shock when performing installation work.
Connect the cable only when the cable is dead!
Observe safety rules for safe work on electrical installation!
WARNING! Fire hazard!
In case of unprofessional connection the clamping may
become very hot. Tighten the cable strands and check the
clamping for correct fit!
7. Attach and press the lid to the bottom part and lock the lid by a
quarter turn (90°) clockwise of the lid fasteners using a flathead
screwdriver.
Ensure correct fit and cleanliness of the lid gasket!
36
Service, maintenance, repair
WARNING
Danger by incorrect servicing, maintenance and repair!
Explosion protection at risk!
- Work is only to be performed by specialist electricians or personnel
trained in electrical engineering with appropriate specialist
knowledge and skills.
- The nature and scope of servicing, maintenance and testing are
based on national regulations.
- Adapt maintenance and testing intervals to operating conditions
- Minimum check:
- Integrity of the box, used cable glands and inserted cables,
- Tightness of the cable junction box by correct closing and clean
lid gasket,
- Correct connection of the cables to the included terminal.
- If necessary correct the connection according to technical data.
- Impermissible heating of the terminal can be determined by
temperature measurement, f. e. via thermographic camera.
- Compliance to permissible temperatures
- Only repair with genuine spare parts