Technical data
Type
Permissible Ex-area in gases
Permissible Ex-area in dusts
IP degree of protection
Dimensions (H x W x D)
Permissible size of cable entries
1)
Drill holes are to be made in the respective
nominal size in mm with a tolerance of up
to +0.5 mm
Number of terminals
Rated insulation voltage
Rated current (I
)
n
per terminal
Permissible conductor sizes
24
RX 0203 T
RX 0205 T
II 3G Ex ec IIC T6 Gc
II 3D Ex tc IIIC T85 Dc
IP 66
93 x 93 x 62 mm
M20
M20
3
5
275 V a.c. / d.c.
0.5 mm²
= 4.9 A
0.5 mm²
0.75 mm²
= 6.5 A
0.75 mm²
1.0 mm²
= 8.2 A
1.0 mm²
1.5 mm²
= 9.8 A
1.5 mm²
2.5 mm²
= 11.5 A
2.5 mm²
4 mm²
= 13.1 A
4 mm²
0.5 - 4 mm² sol
0.5 – 2.5 mm² f
RX 0207 T
93 x 93 x 62 mm
M20
7
275 V a.c. / d.c.
= 4.1 A
0.5 mm²
= 3.3 A
= 5.7 A
0.75 mm²
= 4.9 A
= 7.4 A
1.0 mm²
= 6.5 A
= 9.0 A
1.5 mm²
= 8.2 A
= 10.6 A
2.5 mm²
= 9.8 A
= 12.3 A
4 mm²
= 11.5 A
0.5 - 4 mm² sol
0.5 – 2.5 mm² f
RX 0610 T
II 3G Ex ec IIC T6 Gc
II 3D Ex tc IIIC T85 Dc
IP 66
130 x 130 x 77 mm
130 x 130 x 77 mm
M20, M25, M32
M20, M25, M32
10
690 V a.c. / d.c.
0.5 mm²
= 4.1 A
0.5 mm²
0.75 mm²
= 4.9 A
0.75 mm²
1.0 mm²
= 5.7 A
1.0 mm²
1.5 mm²
= 7.4 A
1.5 mm²
2.5 mm²
= 9.0 A
2.5 mm²
4 mm²
= 10.6 A
4 mm²
6 mm²
= 12.3 A
6 mm²
0.5 – 6 mm² r, f
RX 0614 T
14
= 3.3 A
= 4.1 A
= 4.9 A
= 6.5 A
= 8.2 A
= 9.8 A
= 11.5 A
25