Perm. number and cross section of wires per clamping unit
Built-in terminals have 5 poles and 2 clamping units per pole
Typ
Cu
1-4 x 0.75 mm² r, f
1-4 x 1.0 mm² r, f
KX 0202 C
1-3 x 1.5 mm² r, f
1-2 x 2.5 mm² r, f
1 x 4 mm² r, f
1-4 x 1.5 mm² r, f
1-3 x 2.5 mm² r, f
KX 0404 C
1-2 x 4 mm² r, f
1 x 6 mm² r, f
1-3 x 1.5 mm² r, f
1-2 x 2.5 mm² r, f
KX 0606 C
1-2 x 4 mm² r, f
1-2 x 6 mm² r, f
1 x 10 mm² r, f
28
Rated
Cu
current
1-4 x 0.75 mm² r, f
5.7 A
1-4 x 1.0 mm² r, f
7.4 A
1-3 x 1.5 mm² r, f
10.6 A
1-2 x 2.5 mm² r, f
13.5 A
1 x 4 mm² r, f
18.4 A
1-4 x 1.5 mm² r, f
11.5 A
1-3 x 2.5 mm² r, f
13.9 A
1-2 x 4 mm² r, f
18.4 A
1 x 6 mm² r, f
22.9 A
1-3 x 1.5 mm² r, f
11.5 A
1-2 x 2.5 mm² r, f
14.7 A
1-2 x 4 mm² r, f
19.6 A
1-2 x 6 mm² r, f
23.7 A
1 x 10 mm² r, f
30.7 A
1-3 x 2.5 mm² r, f
1-2 x 4 mm² r, f
KX 1010 C
1-2 x 6 mm² r, f
1-2 x 10 mm² r, f
1 x 16 mm² r, f
Connecting different conductor types or cross sections in one clamping unit is
not permissible.
Conductor types:
r = rigid = solid (sol) and stranded (s)
f = flexible
General
Information about this instruction manual
This instruction manual contains important details for safe installation,
commissioning and maintenance of Ex cable junction boxes.
Disregarding this instruction manual may cause severe damage,
injuries or even death.
Further documentation
Catalogue and datasheets
EU Declaration of Conformity
1-3 x 2.5 mm² r, f
15.5 A
1-2 x 4 mm² r, f
20.0 A
1-2 x 6 mm² r, f
24.1 A
1-2 x 10 mm² r, f
32.3 A
1 x 16 mm² r, f
42.5 A
www.hensel-electric.de
www.hensel-electric.de
29