If the drainpipe drains into a vessel
(tank or other container), this container
should not be sealed and the drainpipe
should not remain immersed in the
water (see fig. 9).
•
The hole (J) through which the conden-
sate pipe passes should always slope
towards the outside (see fig. 10).
The exact position in which to place the
pipe inlet, as compared to the machine,
is shown on the drilling template.
Make sure, in this case, that the
water expelled outward does not
damage or disturb persons or
property.
During the winter this type of
drainage may cause sheets of
ice to form.
When the condensate drainage is fitted, pay much attention not to
compress the rubber hose.
In the event of operation during the winter with temperatures equal
to or lower than 0° C, make sure that the condensate drain pipe is
protected from freezing in order to ensure draining.
In the event of prolonged operation during the winter with temper-
atures below 5°C, install the optional basin heater kit.
2.4.3 -Assembly of the air ducts and external grids
•
After drilling the holes (with the core drill), insert the plastic sheet (H) supplied
with the air conditioner (fig. 11) inside them.
Since the sheet (H) was made for 202 mm holes, you will have to cut off 130
mm from the long side of the sheet for the 162 mm holes (fig. 11).
The sheets must be 65 mm shorter than the length of the wall.
9
10
EN - 17
UNICO R