Motor Parameters - Pentax IPFC 109 Manual De Instrucciones

Ocultar thumbs Ver también para IPFC 109:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

Parameter
Address
XX
Alternance
ON/OFF
Alternance period
XX [h]
COMBO synchrony
ON/OFF
Start delay AUX
t = XX [s]
PI control
Direct/Reverse
Periodic autorun
t = XX [h]
Dry run cosphi
X.XX
Restarts delay
XX [min]

6.6 Motor parameters

Parameters
Rated motor Volt.
XXX [V]
26
Default
IPFC address:
00
00 master
01 to 07 slaves
Function to allow alternating between
the IPFCs connected in COMBO (or
pumps connected in DOL) in order to
allow equal use of each pump in the
OFF
group; master will reorganize the starting
priority of the pumps by checking the life
of each of them.
Maximum difference in terms of hours
between IPFCs in the group.
0
0 stays for 5 minutes.
With this parameter it is possible to
activate the synchronous operation
OFF
(same speed) of the pumps in COMBO.
It is however necessary to appropriately
lower the parameter "f. min. control".
Delay time with which the slaves start
after the variable speed pump has
0
reached the maximum frequency and the
pressure value has fallen below set value
– delta control
Direct: increasing motor speed also
misured value increases
Reverse: increasing motor speed, misured
value decreases.
Pump periodic autorun after XX hours of
inactivity. Value 0 makes function
0
disabled.
Warning, review the advice in chapter 1.
Cosphi value below which the unit stops
0.65
the motor and give "no water" alarm.
Restart delay after a dry running alarm.
10
At each tentative (max 5) restart delay
will be doubled.
Default
XXX
Motor rated voltage (as shown on motor nameplate).
Description
Description
    
    
    