Installation Preparation
TYPE OF ELECTRIC CONNECTIONS
A power supply kit must be used to supply power to the
Zoneline unit.
Models must be installed using the appropriate GE
Appliances power supply kit for the branch circuit
amperage and the electrical resistance heater wattage
desired. See the POWER CONNECTION CHART to
select the appropriate kit.
It is the responsibility of the installer to ensure the
connection of components is done in accordance with
electrical codes.
External Disconnect
There shall be disconnecting means from the electrical
supply located within line of sight of the closet door
opening or access panel opening. The disconnecting
means shall be readily accessible while the air
conditioner is installed in the closet. The disconnect
shall not obscure the rating plate or be located on
the access panel or closet door. A properly rated field
supplied switch is a common means for electrical
disconnection.
POWER CONNECTION CHART
Power Supply Kits
230 / 208 Volt
Range: 187v - 254v
RAK315D
RAK320D
RAK330D
Power Supply Kits
265 Volt*
Range: 249v - 293v
RAK515D
RAK520D
RAK530D
*See NEC for 265 Volt applications
12
Direct Connections
Configuration
Direct Connection
@ 230 / 208 Volt
Hard Wired
Hard Wired
Hard Wired
Configuration
Direct Connection
Hard Wired
Hard Wired
Hard Wired
Power Supply Kit Direct Connect
208/230/265 Volt Applications
Power Supply Kit - Direct Connect
IMPORTANT: Connection to a branch circuit MUST
be done by direct connection in accordance with the
National Electrical Code. Plugging this unit into a
building mounted exposed receptacle is not permitted
by code.
Heater Wattage
2.45 / 2.00 KW
15-Amp Time Delay-Fuse or Breaker
3.45 / 2.82 KW
20-Amp Time Delay-Fuse or Breaker
5.00 / 4.09 KW
30-Amp Time Delay-Fuse or Breaker
Heater Wattage
@ 265 Volt
2.45 KW
15-Amp Time Delay-Fuse or Breaker
3.45 KW
20-Amp Time Delay-Fuse or Breaker
5.00 KW
30-Amp Time Delay-Fuse or Breaker
Circuit Protective Device
Circuit Protective Device
49-5000640 Rev. 1