7.1.2
After an alarm condition
After an alarm, the photoelectric probe must be checked for pollution.
Verify that there are no remainders of the liquid or deposits between the
transmitter and the receiver of the light barrier.
1. Remove remainders of liquid between the transmitter and the receiver.
2. Carefully clean the probe with a dry, lint-free cloth (see "Maintenance").
3. Replace the probe if deposits or encrustation have formed between the
transmitter and the receiver of the light barrier.
4. Perform a function test (see "Performing the function test").
7.2
Use in flood hazard areas
INOPERABLE PRODUCT
•
Verify that the product is replaced after a flood event.
Failure to follow these instructions can result in equipment damage.