Danfoss Optyma Slim Pack OP-LSVM Serie Instrucciones página 50

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 20
Instructions
Annex - A
Technical data (English)
Name plate
A
OP-MSXM108MLW05E
114X7072
B
C
D
E
Fluid Group
1 & 2
F
PED Category
II
G
Application
MBP
H
PS
-1/32 bar
HP
I
PS
-1/21.5 bar
LP
J
PT
32 bar
K
o
TS
-30/ 63
C
HP Switch Pressure
31 bar
Year of Mfg.
2021
L
PR
V Setting
34.5 bar
089
0045
0879
Only for Norway
Address - Danfoss Ltd., 22 Wycombe End, HP9 1NB, GB
Імпортер:ТОВ з іі "Данфосс ТОВ" 04080, Київ 80, п/с 168, Україна
* For exact values please refer name plate in unit
A: Model
B: Code number
C: Serial Number and bar code
D: EAN number
E: Refrigerant
F: PED Category
G: Application, Ingress Protection
H: Maximum Allowable Pressure (HP
side)
Designation system for the Optyma™ Slim Pack range
OP - MSIM
034 ML W05 G
1 2 3 4
5
1 Application
M = MBP
L = LBP
2 Package
Condensing unit family: S = Slim Pack
3 Refrigerant
T = R404A/R507, R455A, R454C, R448A/R449A, R452A
S = R134a, R513A, R1234yf
V = R454C, R455A, R452A, R404A/R507
X = R404A / R507, R134a, R407A, R407F, R448A, R513A, R449A,
R452A
I = R404A / R507, R134a, R407A, R407F, R448A, R513A, R449A,
R452A, R454C, R455A
4 Condenser
M = Microchannel heat condenser
5 Swept volume
Displacement in cm
3:
Example 034 = 34 cm
6 Compressor platform
DP/DX/DS = Fixed speed Reciprocating compressor
MP/MX/MS = Fixed speed Reciprocating compressor,
ML = Scroll compressor
7 Version
W05: Optyma™ Slim Pack standard version (see Version table)
W09: Optyma™ Slim Pack with Fan speed Controller
8 Voltage code
G = 230V/1-phase compressor & fan
E = 400V/3-phase compressor & 230V/1-phase fan
50 | AN37261865152501-010301 - 118A2176C
IP54
Voltage
400V~3N~50Hz
LRA
60 A
MCC
14 A
RLA
8.3 A
A2L
Refrigerant
Danfoss A/S, 6430 Nordborg, Denmark
I: Maximum Allowable Pressure (LP
side)
J: Test Pressure
K: Maximum allowable Design
Temperature
L: Pressure Relief Valve set pressure
6
7
8
3
N
Picture 1 : Minimum mounting distances
L
M
[mm]
[mm]
250
50
Version control
Optyma™ Slim Pack
Condensing unit :IP level
Refrigerant
Compressor technology
Control box (pre-wired E-panel)
Microchannel condenser
Fan speed controller
Main switch (circuit breaker)
Filter drier (flare connections)
Sight glass
Crankcase heater
HP/LP adjustable pressostat
Access door(s)
Acoustic insulation
Discharge gas thermostat
(Provision)
HP/LP Alarm (Provision)
Electrical Box design
Adjustable time delay
(Compressor)
Pressure Relief Valve**
* Compatible with A2L refrigerant
** Accessory (Not factory mounted)
L
O
L
M
N
[mm]
550
W05*
W09*
IP54
IP54
Group 1 / Group 2
Group 1 / Group 2
Reciprocating / Scroll Reciprocating / Scroll
yes
yes
-
-
yes
yes
yes
Auto/Manual reset
Auto/Manual reset
mode
mode
yes for E-Box
yes for E-Box
Provided as accessory.
Not supplied with unit.
yes
yes
IP54
IP54
yes
-
© Danfoss | Climate Solutions | 2022.02
O
[mm]
550
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
-
Tabla de contenido
loading