Important - CARLO GAVAZZI WM50 Manual De Instrucciones

Ocultar thumbs Ver también para WM50:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 190
Page
title/sub-
Page title
menu
Dig out x (x
Function
= output
number)
Pulse type
Pulse weig
Al status
Out test
Power test
Tariff
-
Dig in x (x =
Function
input
number)
Pulse type
Pulse weig
Process
Unit
Probe
Min elect
Max elect
Min displ
Max displ
Description
Function of digital output x
Type of energy (kWh or kvarh)
Weight of pulse (kWh/kvarh per
pulse)
Normal output status
Enable of transmission test
Power value for test
Tariff management
Digital input x function
Value associated with the pulse
totalizer for Puls selection
Pulse weight
Temperature unit of measure
Temperature probe type
Minimum analog input value
Maximum analog input value
Value displayed for minimum analog
input
Value displayed for maximum analog
input
Values
Remo: remote control
Alar: alarm
Puls: pulse output
kWh Pos : imported active energy/ kvarh Pos : imported
reactive energy/ kWh Neg : exported active energy/
kvarh Neg : exported reactive energy
-
Ne : normally closed/ Nd : normally open
Yes/ No
From 0.001 W to 9999 MW
none: disabled
Cloc: via internal calendar and clock
Inp: via digital inputs
Remo: via Modbus command
remo: input read status
Tari: tariff management
Puls: pulse totalizer
Rst: alarm reset
Trip: protection trip totalizer
Sync: average value calculation interval synchronization
command (dmd)
Cont: pulse meter associated with total imported,
exported or imported reactive energy according to the
selected input
IMPORTANT: check which functions are
available for each input, see "Digital inputs"
on page 23
Gas: gas
H2OC: cold water
H2OH: hot water
HEAT: heat
From 0.001 to 9999
Value expressed in kWh, kvarh, m3 or number of trips
per pulse
C: degrees Celsius
F: degrees Fahrenheit
0: PT100 (3-wire)
1: PT100 (2-wire)
2: PT1000 (3-wire)
3: PT 1000 (2-wire)
From - 20mA to 20 mA
From - 20mA to 20 mA
From -9999 to 9999M
From -9999 to 9999M