General Settings - CARLO GAVAZZI WM50 Manual De Instrucciones

Ocultar thumbs Ver también para WM50:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 190
1. Meet all the requirements indicated in "Configuration requirements via UCS" before.
2. Follow the instructions according to how you want the analyzer and PC/smartphone to communicated:
To communicate...
via RS485 network (Modbus RTU) or Ethernet (Modbus TCP/IP)
via direct point to point connection or via OptoProg
3. Start UCS and connect to WM50 via automatic scan or by manually setting correct communication parameters.
4. Open the settings section, set parameters and save changes.
5. Check correct system operations using the data display and read tools included in UCS.
Settings from WM50

General settings

CAUTION! The settings menu automatically closes after 120 s of disuse and all changes are lost.
Note: default values are underlined. Presence of the pages depends on the installed accessory modules, see "Accessory modules
settings" on page 32. To learn more about settings, see "Managed measurements" on page 18.
Page
title/sub-
Page title
menu
Password?
-
Change
-
pass
Backlight
-
Color
-
Modules
MFI6O6 MFI6R4
MATPN
MC485232
MCETH
MABC
System
-
Ct ratio
-
Ctn ratio
-
Dmd
Time
Sync
Set power
Type
Value
Description
Enter current password
Change password
Display backlight time (min)
Back lighting
Module enable
Enable LED ON blinking of TCD12
that monitors the set channels
System type
Current transformer ratio (CT)
Neutral current transformer ratio
Average values calculation interval
(min)
Synchronization type for average
value calculation
Power displayed in the LCD bar
graph
Full range (W or VA)
Then...
setWM50 communication parameters via touch keypad
skip to the next step
Values
Current password
Four digits (from 0 to 9999)
0: always on
From 1 to 255 (2)
0: off
1: white
2: blue
3: blinking if an alarm is active, otherwise off
4: blinking if an alarm is active, otherwise white
5: blinking if an alarm is active, otherwise blue
Yes/ No
Auto: indicates that the module is automatically
recognized by the system
1.12: channels from 1 to 12
13.24: channels from 13 to 24
25.36: channels from 25 to
36 37.48: channels from 37 to 48
49.60: channels from 49 to
61.72: channels from 61 to 72
73.84: channels from 73 to 84
85.96: channels from 85 to 96
1P: single-phase system (2-wire)
2P: two-phase system (3-wire)
3P.n: three-phase system (4-wire)
From 1 to 2000
From 1 to 9999
1/ 5/ 10/ 15 / 20/ 30/ 60
Off: synchronization disabled
CloC: via internal clock
inP: via internal clock synchronized via digital input
VA: apparent power
W: active power
From 1000 to 9999M
WM50 - Instruction manual | 26/04/2022 | CARLO GAVAZZI Controls SpA
Configure the system
29
Tabla de contenido
loading

Este manual también es adecuado para:

Wm50av53hbc

Tabla de contenido