EBARA E-SPD+ Manual De Instrucciones Y Mantenimento página 33

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 155
Par.
Description
Units
5.41
RELAY OUTPUT 1
5.42
RELAY OUTPUT 2
5.43
SCHEDULE OPERATION 1
5.44
PROGRAM START TIME 1
5.45
PROGRAM STOP TIME 1
5.46
SCHEDULE OPERATION 2
5.47
PROGRAM START TIME 2
5.48
PROGRAM STOP TIME 2
OVERPRESSURE ALERT
5.49
LEVEL
PRESSURE DIFFERENTIAL
5.50
ALARM LEVEL
MINIMUM TEMPERATURE
5.51
ºC
ALERT LEVEL
MAXIMUM TEMPERATURE
5.52
ºC
ALERT LEVEL
TEMP. DIFFERENTIAL
5.53
ºC
ALARM LEVE
DRY RUNNING ALARM
5.54
ACTIVE
Programming
Default
Min.
Max.
OFF
Alarm (NO)
Alarm (NC)
Start
Clock (NO)
OFF
Clock (NC)
Dry running
External stop
Overpressure (NO)
Overpressure (NC)
OFF
See parameter 5.41
OFF
M-Su
OFF
M-F
Sa-Su
M ..... Su
00:00
00:00
23:59
00:00
00:00
23:59
OFF
See parameter 5.43
00:00
00:00
23:59
00:00
00:00
23:59
FS
Par 1,1
FS
FS
Par 1,1
FS
0
0
100
100
0
100
100
0
100
YES
YES
NO
33
Notes
The aim of this parameter is to enable signals remotely.
OFF: The relay is never activated.
Alarm (NO): The relay closes before an alarm.
Alarm (NC): The relay opens before an alarm.
Start: The relay is energised when the unit is running.
Clock (NO): The relay closes depending on the time data
programmed in parameters 5.44 to 5.48.
Clock (NC): The relay opens depending on the time data
programmed in parameters 5.44 to 5.48.
Dry running: The relay is energised if the inverter
detects dry running.
External stop: The relay is energised when there
is an external stop. (For this condition we must have
programmed a digital input as "Local Stop").
Overpressure (NO): The relay closes if there is
overpressure alert (parameter 5.49).
Overpressure (NC): The relay opens if there is
overpressure alert (parameter 5.49).
See parameter 5.41
In this parameter you can choose not to have a schedule
program (OFF) or the days of the week that you want
this program to run. You can choose between whole
weeks (M-Su), weekdays (M-F), weekends (Sa- Su) or
individual days.
The schedule program will act on the output relay
programmed for this purpose.
Start time of schedule program 1.
Stop time of schedule program 1.
Same as parameter 5.43 but for a second schedule
program.
Start time of schedule program 2.
Stop time of schedule program 2.
Parameter to set the maximum pressure value of the
Hydraulic system.
Parameter to set the maximum differential pressure value
of the hydraulic system.
Parameter to set the minimum temperature of the
hydraulic system.
Parameter to set the maximum temperature of the
hydraulic system.
Parameter to set the maximum differential temperature
of the hydraulic system.
Parameter for enabling or disabling the low water level
alarm.
In the case of being active and cause notice, the drive will
start attempts by the following sequence:
5 minutes, 15 minutes, 1 hour, 6 hours or 24 hours. The
display shows the remaining time start attempt. Pressing
F2 we force the reset of the notice, still unfinished
countdown.
If after the 24-hour notice is detected again dry running,
the drive will lock indefinitely until you press F2.
EN
Application
A
B
C
D
E
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
(1)
X
X
X
(2)
X
X
(2)
X
X
X
X
X
X
Tabla de contenido
loading

Tabla de contenido