Settings, Safety Checks - Cuenod C 280 B 517/8 Manual De Utilización

Quemadores bicombustible
Ocultar thumbs Ver también para C 280 B 517/8:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Start-up
Adjusting and checking safety devices
Low nitrogen
Burner
oxide type
capacity
NOx
kW
1800
2100
C 280
2500
2850
1800
2100
C 285
2500
2850
2100
2600
C 330
3000
3700
3800
2400
3000
C 380
3600
4000
4100
2400
2800
C 430
3600
4600
On delivery, pump is adjusted at 20 bar ± 0.5 bar.
Regulator at 10 bar ± 0.5 bar
1kg fuel oil at 10°C = 11.86 kW
(1 ) Nozzle equivalents : Steinen 60° SS - Hago 60P, 45 F
Fuel oil
Danfoss Nozzle
flow
(1) US gal/h
45°B or 60° B
st
Kg/h
1
all
152
13.8
177
17.5
211
19.5
240
19.5
152
13.8
177
17.5
211
19.5
240
19.5
202
17.5
253
21.5
303
19.5
337
28.0
320
30.0
202
17.5
253
19.5
303
28.0
337
30.0
346
35.0
202
17.5
236
19.5
303
28.0
388
35.0
Adjusting and checking safety
devices for GAS only
Gas pressure switch.
· Adjust to minimum distribution
pressure.
Burner is working with ignition capacity.
· Close ball valve of fuel slowly.
Burner should stop because of
insufficient gas pressure.
· Open ball valve again.
Burner shall restart automatically.
The pressure switch is adjusted.
· Fit and screw cover on.
Leakage controller :VPS.
· Open pa on the VPS.
· Restart burner.
After 30s, the VPS should lock out to
safety ( red indicator On).
· Close pa.
· Press red indicator light to unlock
the VPS safety.
The control cycle is restarted.
Burner works.
· Check for leakage.
11/2003 - Art. Nr. 13 013 506A
Q GAS and FUEL OIL
Air pressure switch.
Burner is working with ignition capacity.
· Look for air pressure switch cut-off
nd
2
all
(locking).
· Multiply value read by 0.8, in order
13.8
13.8
to arrive at the adjustment point.
19.5
· Restart burner.
24.0
· Gradually choke the air suction inlet.
· Make sure the CO level does not
13.8
exceed 10.000 ppm, prior to locking
13.8
the unit.
19.5
24.0
Otherwise, increase the air pressure
switch adjustment and restart the
13.8
test.
21.5
· Disconnect simultaneously both
28.0
micro ammeter cables.
30.0
Unit should lock out immediately.
30.0
· Fit the measuring bridge and the
covers once more.
19.5
· Disconnect the measuring devices.
28.0
30.0
· Close the pressure take-offs.
35.0
· Unlock the unit.
35.0
Burner works on gas or fuel oil (both
fuels are available).
19.5
· By actuating switch S4, select the
24.0
other fuel. Burner stops... then
30.0
35.0
restarts with chosen fuel.
· Check the following :
for any leaks between the flange
and the boiler front.
that the regulator circuit is open
(limiter and safety).
the intensity on the thermal relays of
the motors.
Cell
· Test the cell with simulated flame
and without flame.
· Check combustion in real operating
conditions (doors closed, cover on,
etc) as well as for leaks in the
various circuits.
When GAS combustion tests are
validated, return to FUEL OIL.
· Check FUEL OIL combustion
values, which should remain
unchanged relative to initial
adjustment.
· Record results on the appropriate
forms and forward them to the
dealer.
· Set to automatic operation.
· Distribute the information required to
operate.
· Place the boiler-room plate in a
conspicuous location.
EN