Parameter Description
Threshold on inlet temperature for evaporator
P49
EC or AC with double speed blower speed
setting
P50
Antifreeze lower water temperature setpoint
P51
Evaporator EC blower higher speed setpoint
P52
Evaporator EC blower lower speed setpoint
P53
EC evaporator fan defrost speed setpoint
P54
Low pressure switch bypass time
Band 1 evaporator temperature proportional
P55
regulation
Differential temperature with activation of
P56
maximum speed
Differential temperature with deactivation of
P57
maximum speed
Use of the evaporator fan with the compressor
P58
off
P59
Evaporator fan speed (EC) with compressor off 0÷100%
Temperature difference 1 of evaporation of the
P60
air for the calculation of the setpoint
Temperature difference 2 of evaporation of the
P61
air for the calculation of the setpoint
Temperature difference 3 of evaporation of the
P62
air for the calculation of the setpoint
Temperature difference 4 of evaporation of the
P63
air for the calculation of the setpoint
Temperature difference 5 of evaporation of the
P64
air for the calculation of the setpoint
Temperature difference 6 of evaporation of the
P65
air for the calculation of the setpoint
Band 2 evaporator temperature proportional
P66
regulation
Band 3 evaporator temperature proportional
P67
regulation
Band 4 evaporator temperature proportional
P68
regulation
Band 5 evaporator temperature proportional
P69
regulation
Band 6 evaporator temperature proportional
P70
regulation
EC evaporator fan speed reduction for silent
P71
mode
P72
EC fan speed regulator gain
(1) = NOT USABLE FOR THIS DEVICE
(2) = ONLY FOR MODELS "EKHHE200PCV37, EKHHE260PCV37"
Page 30
Range
10÷40°C
0÷15°C
60÷100%
10÷60%
0÷100%
1÷240 min
1÷20°C
P57÷20°C
1°C÷P56
0 = OFF
1 = ON with manual speed control
2 = ON with automatic speed control
1÷25°C
1÷25°C
1÷25°C
1÷25°C
1÷25°C
1÷25°C
1÷20°C
1÷20°C
1÷20°C
1÷20°C
1÷20°C
0÷40%
1÷100
Default
Notes
25°C
Modifiable
12°C
Modifiable
90%
Modifiable
50%
Modifiable
50%
Modifiable
1
Modifiable
4°C
Modifiable
2°C
Modifiable
1°C
Modifiable
0
Modifiable
40%
Modifiable
4°C
Modifiable
2°C
Modifiable
6°C
Modifiable
3°C
Modifiable
10°C
Modifiable
18°C
Modifiable
2°C
Modifiable
9°C
Modifiable
5°C
Modifiable
10°C
Modifiable
5°C
Modifiable
15%
Modifiable
5
Modifiable
User, Installations and Maintenance Manual
Tabla de contenido
loading

Este manual también es adecuado para:

Ekhhe200pcv37Ekhhe260cv37Ekhhe260pcv37