REMS Multi-Push S Instrucciones De Servicio página 23

Ocultar thumbs Ver también para Multi-Push S:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 63
eng
n H
O
n-times
water change
2
VA H
2
VS H
2
V H
O
l
used water volume
2
File no.
memory location no. for measuring log
max. DN
largest rated diameter
Enter
next screen display
Esc
previous screen display or cancel
Ver. Software
version software
NOTICE
NOTICE
The defaults for the different test criteria in the Settings menu of the REMS
Multi-Push SL/SLW
SL/SLW
SL/SLW
"Leak tests of drinking water installations with compressed air, inert gas or water"
(January 2011) of the German Central Association for Sanitary, Heating and Air
Conditioning (ZVSHK) as well as the Technical Rule "Technical Rule for Gas
Installations Worksheet G 600 April 2018 DVGW-TRGI 2018" of the DVGW
German Gas and Water Association. All defaults for the test programs can be
edited by the user in the Settings menu and in the Flushing, Test with compressed
air, Test with water and Compressed Air Pump programs
menu are saved, i.e. they reappear the next time the REMS Multi-Push SL/SLW
is switched on. If the defaults are only changed in one of the programs
original defaults appear again the next time the REMS Multi-Push SL/SLW is
switched on. Reset resets all defaults to factory settings and the language to
German and the date, time, units formats to DD.MM.YYYY, 24 h, m/bar.
Attention:
Before using the REMS Multi-Push, check whether the respective latest version
software is installed on the input and control unit. For REMS Multi-Push S the
use of software version as of "03.40, Date 2020-04-08" is permitted. Select the
Settings menu and then Device data to display the version software. The latest
version software (Ver. Software) for the input and control unit is available by USB
the latest version software number and install the latest version software if
necessary.
Download procedure:
3. Save "update.bin" on USB stick
4. Plug the USB stick into the USB port of the REMS Multi-Push
REMS Multi-Push must be switched off for this, switch off with the On/Off button
(Fig. 2 (4)) and pull out the mains plug if necessary. Insert the USB stick with
the latest version software into the USB port (Fig. 2 (33)). Plug the mains plug
into the socket. Press the Reset button (Fig. 1 (2)) of the PRCD fault current
circuit breaker (1). The control lamp (5) lights green. The latest version software
LED, you should wait about 1 minute after switching on the PRCD. The latest
version software is then installed on the input and control unit. Pull out the USB
stick.Switch on REMS Multi-Push with the On/Off button (4). Press the "?"
button (7) within 5 s. Select Device data\Reset in the Settings menu with the
in the Settings menu and the defaults for the individual programs checked and
changed if necessary.
If the "?" button (Fig. 2 (7)) is pressed within 5 s after switching on the REMS
Multi-Push, the Settings menu opens. The desired line is selected on the screen
and reduced with the arrow pointing to the left. The values change faster when
hand corner of the screen respectively. The complete selection of the screen
The previous screen appears if the Esc button (10) is pressed during the setting.
Already changed values are rejected.
If the Esc button (10) is pressed during the stabilisation/wait time (t stabi), the
program aborts, the values (useless) are still saved, appear on the screen and
"Cancel" appears additionally on the screen and possibly on the print strip.
If the Esc button (10) is pressed during the test time (t test), the values are still
saved, appear on the screen and "Cancel" appears additionally on the screen
and possibly on the print strip. In the test programs Enter provides a shortcut
for the adaptation of p actual to p refer.
Select language
nguage, , Enter:
Default German (deu) is preselected. Another language can be selected with
programs. Changes in the Settings
programs, the
SL/SLW
SL/SLW is
Select date, Enter:
, Enter:
Format "DD.MM.YYYY" is defaulted for the date. Another format for the date
Select time, Enter:
e, Enter:
Default "24 hours" is preselected. Another format for the time can be selected
Select defaults \ units, Enter:
Select defaults \ units, Enter:
Default "m / bar" is preselected. Other units can be selected with the arrow
Select Defaults \ Defaults \ Leak test with compressed air, Enter (REMS Multi-
Select Defaults \ Defaults \ Leak test with compressed air, Enter
Push SL/SLW):
Push SL/SLW)
necessary.
Defaults \ Defaults \ Testing gas installations with compressed air \ Select load
Defaults \ Defaults \ Testing gas installations with compressed air \ Select load
testing, leak testing, Enter (REMS Multi-Push SL/SLW)
testing, leak testing, Enter
(REMS Multi-Push SL/SLW):
necessary.
Select Defaults \ Defaults \ Load test with compressed air \ DN, Enter
ct Defaults \ Defaults \ Load test with compressed air \ DN, Enter (REMS
Multi-Push SL/SLW):
Multi-Push SL/SLW)
necessary.
Select Defaults \ Defaults \ Test with water, method A or B or C, Enter
t Defaults \ Defaults \ Test with water, method A or B or C, Enter (REMS
Multi-Push SLW):
Multi-Push SLW)
necessary.
Select device data, Enter:
Select device data, Enter:
Enter. "Reset" resets all defaults to factory settings and the language to German
(deu) and the date, time, units formats to "DD.MM.YYYY", "24 h", "m/bar".
2.4.1 Flushing EN 806-4
mittent compressed air and with water-air mixture with constant compressed
air, REMS Multi-Push must be connected to the water supply or the manifold
of the installation (Fig. 3) as follows:
2.4.2 Flushing
1717:2000 after the house connection (water meter) (Fig. 5) to prevent contam-
drinking water lines any more after they have been used for heating systems.
WARNING
WARNING
The European standard EN 806-4:2010 prescribes the following for the
"Selection of disinfectants":
by a responsible person or authority."
"All chemicals that are used for the disinfection of drinking water installations
must meet the requirements for chemicals for water treatment which are spec-
national standards and technical rules."
"Disinfectants must be used and applied in agreement with the appropriate EC
directives and all local or national regulations."
"Transport, storage, handling and use of all these disinfectants can be dangerous,
therefore health and safety regulations must be strictly observed."
In Germany
Germany the Technical Rules – Worksheet DVGW W 557 (A) October
mends hydrogen peroxide H
O
, sodium hypochlorite NaOCl and chlorine
2
2
dioxide ClO
for the disinfection of drinking water installations.
2
User friendliness, work protection and environmental protection etc. must be
considered in the choice of disinfection chemicals. It should be noted that, when
using oxidants containing chlorine (sodium hypochlorite NaOCl and chlorine
dioxide ClO
), for example, chlorine organic compounds may form which are
2
to be considered harmful to the environment.
REMS therefore recommends disinfecting drinking water installations with
REMS Peroxi (hydrogen peroxide H
alternative with regard to use friendliness, work protection and environmental
protection because it decomposes into hydrogen and water when used and
eng
(REMS Multi-
(REMS
(REMS
recom-
O
). Hydrogen peroxide offers the better
2
2
23
Tabla de contenido
loading

Este manual también es adecuado para:

Multi-push slMulti-push slw

Tabla de contenido