Led Indications - Victron energy MultiPlus 12/1600/70 Manual

Ocultar thumbs Ver también para MultiPlus 12/1600/70:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 89

3.3 LED Indications

LED off
LED flashes
LED illuminated
Inverter/Charger/
6
On / Off / Charger-only switch = On
The inverter is switched on and supplies power to the load.
On / Off / Charger-only switch = On
The inverter is switched on and supplies power to the load.
Pre-alarm: overload, or
battery voltage low, or
inverter temperature high.
On / Off / Charger-only switch = On
The inverter is switched off due to one of the following alarms:
overload, or
battery voltage low, or
inverter temperature high, or
DC ripple voltage too high.
On / Off / Charger-only switch = On
The AC input voltage is switched through and the charger operates in
float mode.
On / Off / Charger-only switch = On.
PowerControl and PowerAssist:
The AC input is switched through and the charge current is zero.
The inverter is switched on and, in case of PowerAssist, assists the AC
input by supplying additional power to the load (see section 2.1).
On / Off / Charger-only switch = On.
Energy
Storage System (ESS):
The AC input voltage is switched through.
The inverter is switched on and supplies power to the load, or excess
power to the mains.
Tabla de contenido
loading

Este manual también es adecuado para:

Multiplus 24/1600/40Multiplus 48/1600/20

Tabla de contenido