3.4 LED Indications

LED off
LED flashes
LED illuminated
Inverter
inverter
charger
alarm
inverter
charger
alarm
inverter
charger
alarm
on
The inverter is switched on and supplies
off
power to the load. Battery operation.
charger only
The inverter is switched on and supplies
on
power to the load.
Pre alarm: overload, or
off
battery voltage low, or
inverter temperature high
charger only
The inverter is switched off.
on
Alarm: overload, or
battery voltage low, or
off
inverter temperature high, or
DC ripple voltage on battery
terminal was too high.