Power Module Features
Communication Interface
22
Dry Contacts: #1 (UPS Normal); #2 (Load On Reserve); #3 (Load On Battery); #4 (Battery Low Voltage);
#5 (Reserve Abnormal); #6 (Battery Test Fail). See "Communications" for details.
23
Remote "Emergency Power OFF" (EPO) Connector: This modular jack allows remote emergency
shutdown. See "Communications" for details.
24
"Smart" RS-232 Interface Port: This female DB9 port connects the UPS to a workstation or server. It
uses RS-232 communications to report UPS and power conditions. It is used with Tripp Lite software and
cabling. See "Communications" for details.
25
Ethernet Port & Ethernet Power: The Ethernet Port is an RS-232 port that accepts an optional RS-232/RJ45
Ethernet Adapter (sold separately). The Ethernet Power connection provides 12VDC power to the
optional adapter. See "Communications" for details.
Generator Contact: This port connects to an auxiliary power generator. When the generator is operating
26
to support the equipment load, the UPS System will automatically reduce its charge current by 50% in order
to prevent overloading of the generator. See "Communications" for details.
RS-485 Ports: These ports allow multiple UPS power modules to be connected in a parallel configuration.
27
See "Communications" for details.
UPS Parallel Communication Ports: These ports allow multiple UPS power modules to communicate
28
while in a parallel configuration. See "Communications" for details.
Installation
Follow all warnings listed in the Safety section prior to installation. The following checklist provides a general guide rather than a complete outline
of procedures.
Installation Checklist
K The floor area where the UPS will be installed has enough supporting strength. See Floor Weight Loading Table on the 3-Phase
UPS Specifications Addendum—50kVA & Above.
K The entrances and hallways to the facility provide enough room for UPS transportation.
K The room where the UPS will be installed has enough clearance around the UPS modules to allow adequate ventilation and access for operation
and maintenance.
K The facility's air conditioning can maintain ideal temperature and humidity levels.
K Noise abating devices are installed (if desired).
K Electrical wiring is clearly marked (for polarity and phase) and checked for compliance with local electrical codes.
K The input power source has been switched off prior to hardwire connection.
K The room where the UPS will be installed includes floor, ceiling and walls made of flameproof materials. The room includes a fire
extinguisher. The room is secure from access by unauthorized personnel.
K All personnel are sufficiently trained for normal and emergency operations.
K During installation, the UPS input neutral is solidly connected to the utility power neutral.
(continued)
5
22
23
24
25
26
27
28