Maintenancemaintenance; General Instructions; Preventive Maintenance; Refrigerant - Parker Hyperchill Plus Serie Manual De Uso

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

4.9 Alarm/Warning history
set
ALHi
esc
set
HySP
esc
set
0
1
2
esc
set
HySP
HySt
HySd
HySC
esc
set
set
set
esc
esc
18.06
13.46
04
Menu
Code
DESCRIPTION
HySP
Alarm number
HySC See alarm code
See day and month of the alarm
HySd
(if the clock option is present)
ALHi
See hour and minutes of the alarm
HySt
(if the clock option is present)
HyS1
b1 temperature at time of the alarm
HyS2
b2 temperature at time of the alarm
HyS3
SET conditions at time of the alarm
set
Press the button "
" to enter in the menu, using the buttons "
" select the parameter " ALHi".
"and "
set
Press the button "
" to enter in the menu, using the buttons "
"and "
" select the parameter "HySP".
set
Press the button "
" to enter in the menu, using the buttons "
"and "
" select the alarm number insert (0,1,2......39) and confi rm
set
with "
" (the number 0 is the last alarm started) .
English
"HySP" appears again, press "
alarm: "HySC" code (es:HP), "HySd" Date (day, month), "HySt" hour
(hour, minutes), "HyS1" "HyS2" "HyS3" sensor b1, b2 and set when the
alarm occurred.
esc
Press "
" to exit.
4.10 Automatic restart
In the event of a power failure, when power is restored the chiller will
assume the On-Off status held at the moment the power was lost.
5

MaintenanceMaintenance

a) Th e machine is designed and built to guarantee continuous operaa)
Th e machine is designed and built to guarantee continuous opera-
tion; however, the life of its components depends on the mainte-
nance performed.
b) When requesting assistance or spare parts, identify the machine
(model and serial number) by reading the dataplate located on the
unit.
HyS1

5.1 General instructions

!
set
esc
Before performing any maintenance, make sure the power to the
refrigerator is disconnected.
28
Y
Always use the Manufacturer's original spare parts: otherwise the
Manufacturer is relieved of all liability regarding machine malfunction-
ing.
Y
In case of refrigerant leakage, contact qualifi ed and authorized
personnel.
Y
Th e Schrader valve must only be used in case of machine malfunc-
tion: otherwise any damage caused by incorrect refrigerant charging
will not be covered by the warranty.

5.2 Preventive maintenance

To guarantee lasting maximum chiller effi ciency and reliability, carry
out:
Z
a)
every 4 months - clean the condenser fi ns and make sure com-
pressor electrical absorption is within the dataplate values;
Z
b)
Every 3 years - installation of kit for maintenance every 3
years.(par.7.5)
• kit for maintenance every 3 years;
• service kit;
• individual spare parts.

5.3 Refrigerant

Z
Charging: any damage caused by incorrect charging carried out by
set
" to enter and see the date of the
ICEP007-024 (60Hz)
unauthorized personnel will not be covered by the warranty.
Y
Th e equipment contains fl uorinated greenhouse gases.
At normal temperature and pressure, the R407C refrigerant is a col-
ourless gas classifi ed in SAFETY GROUP A1 - EN378 (group 2 fl uid
according to Directive PED 2014/68/EU);
GWP (Global Warming Potential) = 1774.
!
In case of refrigerant leakage, air the room.

5.4 Dismantling

Th e refrigerant and the lubricating oil contained in the circuit must be
recovered in conformity with current local environmental regulations.
%
frame and panels
steel/epoxy resin polyester
tank
aluminium/copper/steel
pipes/collectors
copper/aluminium/carbon steel
pipe insulation
NBR rubber
compressor
steel/copper/aluminium/oil
condensator
steel/copper/aluminium
pump
steel/cast iron/brass
fan
aluminium
refrigerant
R407C (HFC)
valve
brass/copper
electrical cable
copper/PVC
Recycling
Disposal
7 / 8
Tabla de contenido

Solución de problemas

loading

Tabla de contenido