Daikin EWAD~C-SS Manual De Instrucciones página 17

Ocultar thumbs Ver también para EWAD~C-SS:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 49
Freecooling system with 2 Way valves
EWADC12CF-XS/XL ÷ EWADC16CF-XS/XL - EWADC11CF-XR ÷ EWADC15CF-XR
EEWT = Water entering temperature probe
ELWT = Water leaving temperature probe
System change over is controlled by embedded unit controller, depending from operating conditions and unit setpoint. Between
winter and summer operation the water side pressure drops are different, consequently the chiller water flow could be different.
Evaluate that the minimum and maximum water flow, between summer and winter operation, are inside the water flow limits (see
product manual).
D-EIMAC00604-14EU - 17/196
Tabla de contenido
loading

Tabla de contenido