8.2. MODBUS MEMORY MAP
Holding registers
N°REG.
Register
0
TipoMotor
1
ModoFun
2
SensorPI
3
Sensor1
4
Sensor2
5
PIRange
6
SetPoint
7
Kp
8
Ki
9
Kq
10
PulsosEncoder
11
MinOut
12
MaxOut
13
S1Alarm
14
S2Alarm
Min.
Max.
Description
0
1
0=PI_Presión
1=PI_Caudal
2=Proporcional
3=Max-Min
0
7
4=PI_Presión+RTC
5=PI_Caudal+RTC
6=Proporcional+RTC
7=Max-Min+RTC
0=Interno
1=IN1 0-10V
0
4
2=IN1 4-20mA
3=IN2 0-10V
4=IN2 4-20mA
1=0-10V %HR
2=4-20mA %HR
3=0-10V °C
0
7
4=4-20mA °C
5=0-10V CO2
6=4-20mA CO2
7=NTC 100K
1=0-10V %HR
2=4-20mA %HR
0
6
3=0-10V °C
4=4-20mA °C
5=0-10V CO2
6=4-20mA CO2
50
1250
SensorPI=0
50
2500
SensorPI<>0
100
9900
Sensor<>0
0=Interno
1=IN1 0-10V
2=IN1 4-20mA
0
5
3=IN2 0-10V
4=IN2 4-20mA
5=ConsolaMODBUS
(PROSYS ECOWATT)
1
250
Increases 1
1
250
Increases 1
50
300
Increases 1
0
16
Increases 1
0
50
Increases 5%
50
100
Increases 5%
0
100
Increases 5%
0
100
Increases 5%
Default
0=AC
1
1=DC
0
0
0=NO
0
0=NO
0
400
(CAB-125/150/160 ECOWATT)
500
(CAB-200/315 ECOWATT)
650
(CAB-250 ECOWATT)
550
(CAB-355/400 ECOWATT)
5
20
20
50
(CAB-125 ECOWATT)
56
(CAB-150/160 ECOWATT)
81
(CAB-200 ECOWATT)
88
(CAB-250 ECOWATT)
108
(CAB-315 ECOWATT)
136
(CAB-355 ECOWATT)
81
(CAB-400 ECOWATT)
2
5
1
25
100
90
90
63
Comments
Motor type
Operation mode
Sensor type in PI
PRESSURE or PI VOLUME
mode
Sensor type in
PROPORTIONAL mode
and analog input signal 1
Sensor type in
PROPORTIONAL mode
and analog input signal 2
Range sensor in PI
PRESSURE mode
Set point in PI PRESSURE
mode
Proportional constant in PI
PRESSURE mode
Integral constant in PI
PRESSURE mode
Airflow constant with
pressure sensor
Number of pulses for
encoder lap
Minimum output value
Maximum output value
Analog input 1 alarm
Analog input 2 alarm