EN
– adjust the air thermostat and check that the boiler starts and
operates correctly
– carry out the procedure "Chimney sweeper function",
to check the mains gas pressure, detect the combustion
parameters and to measure the combustion efficiency
required by legislation in force.
3.3
Parameter setting and display
To go into the parameter menu:
– from the selected mode (eg. WINTER)
– press the buttons
r
and
at the same time until "PAR 01" (parameter number) and the
value set (0÷4) appears on the display
3.4
List of parameters
Type
No.
Description
PAR
01
Index showing boiler power in kW
PAR
02
Hydraulic configuration
PAR
03
Gas Type Configuration
PAR
04
Combustion configuration
PAR
08
External sensor value correction
PAR
09
Ignition fan speed
PAR
10
Boiler Antifreeze Threshold
External Sensor Antifreeze Threshold
PAR
11
-- = Disabled
PAR
12
Heating Curve Incline
PAR
13
Minimum Heating Temperature Adjustment
PAR
14
Maximum Heating Temperature Adjustment
PAR
15
Maximum power heating
PAR
16
Heating Post-Circulation Time
PAR
17
Heating Pump Activation Delay
PAR
18
Heating Re-ignition Delay
t
(for approximately 5 seconds)
CONFIGURATION
DOMESTIC HOT WATER - HEATING
– press the button
t
to scroll up the list of parameters and then
r
to scroll down the list
holding the buttons
NOTE:
scrolling movement.
– once the required parameter has been reached, press the
buttons
>
or
<
to modify the value within the permitted range.
The modifications are stored automatically.
When all the parameter modifications have been made, exit the
parameter menu by pressing and holding down the buttons
and
t
all at the same time
screen is displayed.
Range
0 = 25T kW
1 = 25/55 kW
3 = 30/55 kW
0 = rapid
1 = storage tank with thermostat or heating only
2 = hot water tank with sensor
3 = bithermic
4=instant with solar power input
5 = open vent
6 = boiler with heat pump
0 = G20
1 = G31
2 = G230
0 = sealed chamber with combustion control
1 = open chamber with smoke thermostat
2 = Low Nox
-5 .. +5
80 .. 160
0 .. +10
-9 .. +5
0 .. 80
20 .. PAR 14
PAR 13 .. 80
0 .. 100
0 .. 99
0 .. 60
0 .. 60
r
or
t
increases the speed of the
for at least 5 seconds until the initial
U/M
Step
Default
-
1
-
1
-
1
-
1
°C
1
RPMx25
1
°C
1
°C
1
-
1
°C
1
°C
1
%
1
seconds
1
x 10
seconds
1
x 10
Min
1
r
1 or 3
2
0
0
0
128
3
-2
20
20
80
100
3
0
3
89