Siemens ADM-Q12T Manual De Instrucciones página 3

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 7
en
Instruction
ADM-Q12T motion detector
The detector detects movement in the
room under surveillance
7
and initiates
an alarm. It responds most sensitively to
movement in the directions indicated by
arrows
7
B / D. Antimask ensures that
manipulation close to the detector
(0.5 meters) is reliably detected. The
back tamper recognizes if the detector is
removed with force.
Prerequisites
The detector should be installed by peo-
ple with specialist knowledge and in
compliance with valid regulations.
The detector is only intended
for inside rooms. Note the
positioning instructions
Opening the detector
1. Check the scope of delivery
2. Slide up the screw-on cover
loosen the screw
2
B.
3. Pull the housing front
2
D off the base
2
C.
Fitting the detector
1. Fit the mounting base
2
C as follows:
- Define type of fastening
4
A / B. (also
refer to mounting bracket option)
- Break open three fixing holes.
- Break open aperture for cable
feedthrough
4
D.
- Fit mounting base at the proposed
height.
The mounting base should be
secured using two screws
4
A / B and the back tamper
with one screw
C.
4
2. Wire the power supply, alarm and
tamper connections according to the
options provided by the panel
Please note the end-of-line
usage guidelines for simplified
installation using the end-of-
line (EOL) concept
3. Fold front
2
D back onto mounting
base
2
C and secure with screw
Slide down screw-on cover
All manuals and user guides at all-guides.com
Programming
To adjust the settings to the application,
move the switches into the correspond-
ing positions:
LED on / off
5
A
LED only indicates motion in
walk test mode.
LED lights up when detecting
motion.*
* factory setting
PIR sensitivity
Low sensitivity, for harsh
environments.
6
.
High sensitivity, for quiet envi-
ronments.*
* factory setting
.
1
2
A and
Pet immunity
5
Suppresses alarm for pets up
to a weight of 30 kg.
Suppresses alarm for pets up
to a weight of 12 kg.*
* factory setting
Panel
5
to suppress pet detection
For EN 50131-2-2 grade 3 sur-
veillance, move the panel back
to its original position
Sensitivity setting
-
+
*
Turn potentiometer
the position required to
adjust detector to room size
and field of vision.
* factory center is the middle position
8
.
(12-meter field of vision)
Walk test
Move the LED switch
the alarm control panel to walk test mode.
5
E /
9
.
Look at the LED for verification
the walk test for alarm triggering in the
whole detection area
2
B.
A.
2
Options
White light filter AO-WL10k
The white light filter is needed for applica-
tions with extreme white light interference
(> 4000 lux).
Loosen the lens currently at the positions
shown in
tor. Insert adapter
press the lens back down.
Wall & ceiling mounting brackets
The mounting brackets AZ-MBG3
(ceiling
be used to swivel the detector ± 45°. Use
5
A
AZ-MBG3 with switch
installations.
Technical data
Detection area cov-
erage
wide angle
Connections
A
Supply voltage
Max. ripple
Power consumption
D must be pressed in
Current limit
5
G.
Alarm output
Alarm holding time
5
F.
Tamper contact
Antimask
5
D
5
D into
Control input
Self test – Fault
Warm up period
Pet immunity
EMI rejection up to
5
A to ON or move
2 GHz
Operating tempera-
. Run
ture
Storage tempera-
7
of the detector.
ture
Air humidity
EN 60721
Type of housing
protection
EN 60529
EN 50102
- 3 -
5
F and remove from the detec-
3
B in to detector and
10
10
B and wall
10
C mounting) can
10
D for EN grade 3
12 m
7
B
Power supply
(2x)
Alarm (2x)
Tamper (2x)
Antimask (2x)
9.6 ... 16 V
DC
(12 V
nominal)
DC
1 V
SS
Max. 29 mA
Max. 0.9 A
Opens during
alarm
2 ... 3 s
Opens during
alarm
Opens during
alarm
Walk test
(on: +12V)
Red LED: on
Trouble relay: open
60 ± 5 s
< 12 kg
< 30 kg
> 10 V/m
-10 °C ... +50 °C
-20 °C ... +60 °C
< 85 % rF
not condensing
IP41 / IK02
en
10
A