Test Run & Fault Code
Before Test Run
• Before switching it on, test the supply terminal tier (L, N terminals) and grounding points with 500V megaohm meter and
check if the resistance is above 1MΩ. It can't be operated if it is below 1MΩ.
• Connect it to the power supply of outdoor units to energize the heating belt of the compressor. To protect the
compressor at startup, power it on 12 hours prior to the operation.
Check if the arrangements of the drainpipe and connection line are correct.
The drainpipe shall be placed at the lower part while the connection line placed at the upper part. Heat preservation
measures should be taken such as winding the drainpipe esp. in the indoor units with heating insulating materials.
The drain pipe should be made a slope type to avoid protruding at the upper part and concaving at the lower part on the
way.
Checkup of Installation
check if the mains voltage is matching
check if there is air leakage at the piping joints
check if the connections of mains power and indoor & outdoor
units are correct
check if the serial numbers of terminals are matching
Ways of Test Run
Do ask the installation personnel to make a test run. Take the testing procedures according to the manual and check if the
temperature regulator works properly.
When the machine fails to start due to the room temperature, the following procedures can be taken to do the compulsive
running. The function is not provided for the type with remote control.
• Set the wired controller to cooling/heating mode, press "ON/OFF" button for 5 seconds to enter into the compulsive
cooling/heating mode. Repress "ON/OFF" button to quit the compulsive running and stop the operation of the air
conditioner.
Fault Remedies
When any fault appears, consult the fault code of line control or the flashing times for LED5 of computer panel of indoor
units/health lamp of receiving window of remote control and find out the faults as shown in the following table to remove
all faults.
Indoor Unit Faults
PCB LED5(Indoor Units)/
Failure code at
Receiver Timer Lamp(Remote
wired controller
01
02
03
04
05
06
07
08
09
0A
0C
0E
Outdoor Unit
Code
Fault Descriptions
Controller)
1
Fault of indoor unit ambient temp. transducer TA
2
Fault of indoor unit pipe temp. transducer TC1
3
Fault of indoor unit pipe temp. transducer TC2
4
Fault of indoor unit dual heat source temp. transducer
5
Fault of indoor unit EEPROM
6
Fault of communication between indoor & outdoor units
7
Fault of communication between indoor unit and wired control
8
Fault of indoor unit water drainage
9
Fault of duplicate indoor unit address
10
Reserved
12
Fault of zero cross sing
14
Fault of DC fan
20
Corresponding faults of outdoor units
check if the installation place meets the requirement
check if there is too much noise
check if the connecting line is fastened
check if the connectors for tubing are heat insulated
check if the water is drained to the outside
check if the indoor units are positioned