Lamborghini Caloreclima 55 PM/M-E Prospecto Para El Uso página 13

Quemadores a gas modulantes con dos etapas progressivas
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

solely by means of those openings that feed air to the burner; a second CO2 measurement should then
be taken with the door open.
The level of CO
should not vary very much from the first to the second case.
2
● Should there be more than one burner and one fan in the same room, then this test must be carried out
with all the appliances working at the same time.
● Never cover up the burner room's air vents, the burner's fan's air-intake openings, or any existing air
ducts or air gratings, thus avoiding:
- the formation of poisonous/explosive mixtures of gases in the burner room;
- combustion with insufficient air , which would be dangerous, costly and cause pollution.
● The burner must at all times be protected from rain, snow and freezing.
● The room where the burner is housed should be kept clean at all times, and there should be no volatile
substances in the vicinity, substances which could be sucked into the fan and could block up the internal
ducts of the burner or of the combustion head. Dust can be extremely harmful, particularly when it gets
onto the fan blades as this reduces ventilation and leads to pollution during combustion. Dust can also
build up on the rear of the flame stability disk on the combustion head, leading to a poor air-fuel
mixture.
● The burner must be fed with the type of fuel for which it was designed, as indicated on the data plate
and in the technical characteristics given in the present manual.
- the fuel feed line must be sealed and must be of the rigid variety.
Furthermore, the feed line must be furnished with those regulation and safety devices required by
current local regulations.
Be particularly careful to ensure that no foreign bodies get into the feed line during installation .
● Ensure that the electrical power supply used conforms to those technical characteristics given on the
data plate and in this present manual.
In accordance with current regulations, the electrical system must be connected to an efficient earth
system. The earth cable must be a couple of cm longer than the phase and neutral wires.
Should there be any doubts as to the correctness of the earthing, then this must be checked by a
qualified technician.
Never exchange neutral and phase wires.
Upstream of the equipment, install an omnipolar switch with an opening between contacts of at least 3
mm, as required by the laws in force.
The entire electrical system, and in particular cable cross-sections, should conform to the maximum
absorbed capacity indicated on the data plate and in the present manual.
Should the burner's mains cable be found to be faulty, it should only be replaced by a qualified technician.
Never touch the burner with wet parts of the body or in bare feet.
Never stretch the mains cables, and keep them well away from hot parts or other heat sources.
The length of those cables used must enable the burner to be opened, as well as the boiler door.
All electrical connections must be made by qualified personnel, in strict accordance with existing electricity
regulations.
● Having taken out all the parts from the box, check the contents and make sure that nothing has been
damaged during transportation. Should you have any doubts, do not use the burner but get immediately
in touch with the supplier.
All packaging material (wooden crates, cardboard, plastic bags, foamed plastic, clips, etc...) is a
potential source of both pollution and danger should it be left lying around, and as such should be
collected up and disposed of in the correct fashion (in a suitable place).
All manuals and user guides at all-guides.com
13