4.1.
TERMINAL BOARD M1
4.1.1 Open A
Terminals "OPEN A - COM 2". Normally open contact. Connect, to these terminals, any device (push-button, key selector, etc.) that
commands total opening of the gate. The operation of this contact is defined by parameter D.
NB.:
•An OPEN A pulse, total opening, always has priority on OPEN B, partial opening.
•To install several pulse generators, connect the contacts in parallel.
4.1.2 Open B
Terminals "OPEN B - COM 2". Normally open contact. Connect, to these terminals, any device (push-button, key selector, etc.) that
must command partial opening of the leaf. Partial opening is non-adjustable and equals 30% of the memory-stored total opening.
NB.:
• An OPEN A pulse, total opening, always has priority on OPEN B, partial opening.
• To install several pulse generators, connect the contacts in parallel.
4.1.3 STOP command
Terminals "STOP - COM 2". Normally closed contact. Connect, to these terminals, any safety device (push-button, key selector, etc.)
that must stop gate movement. The status of this input is signalled by LED DL2 "STOP".
NB.:
• If no STOP devices are connected, jumper connect the input.
• To install several STOP devices, connect the normally closed contacts in series.
4.1.4 Closing safety devices
Terminals "FSW CL - COM 2". Normally closed contact. Connect, to these terminals, any safety device (photocells, safety edge, etc.)
that must control gate closing motion by reversing gate movement up to the maximum memory-stored opening. The status of this
input is signalled by LED DL3 "FSW-CL".
NB.:
• If no closing safety devices are connected to the closing motion, jumper connect the input.
• To install several safety devices on the closing motion, connect the normally closed contacts in series.
4.1.5 Opening safety devices
Terminals "FSW OP - COM 2". Normally closed contact. Connect, to these terminals, any safety device (photocells, safety edge, etc.)
that must control gate opening motion by stopping its movement. When the safety device is released, motion will resume normally,
executing the memory-stored cycle. The status of this input is signalled by LED DL4 "FSW-OP".
NB.:
• If no safety devices are connected to the opening motion, jumper connect the input:
• To install several safety devices on the opening motion, connect the normally closed contacts in series.
4.2
M2 TERMINAL BOARD
4.2.1 Encoder
Terminals "SIG. - -ENC - +ENC". Use the encoder supplied with the control unit. On the "SIG" terminal: connect the return signal from
encoder terminal "S11"; connect encoder terminal "-12" to the "-ENC" terminal; connect encoder terminal "+13" to terminal
"+ENC".
NB.:
• The encoder must be used for operation of the control unit
• For encoder operation, observe the connection between terminals as described above.
4.2.2 Closing limit switch (optional)
Terminals "COMF - FCC". Normally closed contact. Connect the closing limit-switch, if any, to these terminals. The switch operates
by stopping the gate closing motion. The status of this input is signalled by LED DL5 "FCC".
NB.:
•If no closing limit-switch is used, the input must be jumper connected.
4.2.3 Opening limit switch (optional)
Terminals "COMF - FCA". Normally closed contact. Connect the opening limit-switch, if any, to these terminals. The switch operates
by stopping the gate opening motion. The status of this input is signalled by LED DL6 "FCA".
NB.:
• If no opening limit-switch is used, the input must be jumper connected.
4.3
M3 TERMINAL BOARD
4.3.1 Flashing Lamp
Terminals "LAMP - LAMP". Use a flashing-lamp with steady light (flashing is produced by the control unit) on operating voltage of 24
Vdc 15W max. It is recommended to connect the flashing lamp before programming the control unit, because its phases are
displayed. A 1.5 sec. pre-flashing steady light goes on during both opening and closing. When the gate is open, the flashing-lamp
is OFF, and only flashes when the closing safety devices are engaged for a maximum time of 10 sec, signalling that one is operating
in the gate movement area, after which the flashing-lamp goes OFF even with the closing safety devices still engaged.
4.3.2 Motor
Terminals "CHM1 - APM1". Connect, to these terminals, the motor with a power supply of 24Vdc 70W max.
4.4 TERMINAL BOARD M4
4.4.1 Power supply
Terminals "VAC - VAC". Connect, to these terminals, the secondary winding wires arriving from the toroidal transformer with voltage
of 22V~ 50 Hz. Power ON is indicated by the lighting up of LED DL1 "POWER".
4.4.2 Batteries (optional)
Terminals "+BAT - - BAT". Connect the 2 buffer batteries (optional) to these terminals. When the control unit is powered, it will keep
the batteries charged. The batteries come into operation when the transformer does not supply power.
NB.:
• For battery dimensions and characteristics, refer to the descriptions on the table in paragraph 2.
• Power supply provided by the batteries should be considered an emergency situation. The number of possible manoeuvres
depends on the quality of the batteries, the gate's structure (weight, length, general conditions, etc.), and on the time since
power was cut, etc, etc.
• Observe the battery supply polarity.