User Mode Setpoint. This option is used to configure the set point temperature of each
user mode for each zone.
o Comfort. Heating mode: 15 to 30˚C / 59 to 86˚F, by default 20˚C / 68˚F. Cooling mode: 18
to 30˚C / 64 to 86 ˚F, by default 24˚C / 75˚F.
o Eco. Heating mode: 15 to 30˚C / 59 to 86˚F, by default 19˚C / 66 ˚F. Cooling mode: 18 to
30˚C / 64 to 86 ˚F, by default 25˚C / 77˚F.
o Unoccupied. Heating mode: 15 to 22˚C/ 59 to 72˚F, by default 17˚C / 63˚F. Cooling mode:
24 to 30˚C / 75 to 86 ˚F, by default 27˚C/81 ˚F.
EN
o Vacation. Heating mode: 10 to 16˚C / 50 to 61˚F, by default 10˚C / 50˚F. Cooling mode: 29
to 35.5˚C/ 84 to 96 ˚F, by default 35˚C / 95 ˚F.
•
Weight. This option is used to set the weight of each zone for purposes of determining
system operation. The weight of the zone will be used for calculating the mode (auto-
change over) or for calculating heat demands when using auxiliary heat. Options: Auto or
Manual.
o Auto (by default). The weight of each zone is automatically assigned based on the
number of zones.
o Manual. Enables to manually define the weight of the zone. Values: 0 to 100.
•
Reset thermostat. (Not available in remote zones). This allows you to reset the thermostat
by returning to the initial settings menu.
AIRZONE THINK
•
System address. (Not available on systems with BACnet gateway). This allows you to define
the number of the system in your installation.
•
Use mode. This allows you to configure the thermostat for the system's different zones
in Basic or Advanced mode. By default, it is set to Advanced. The parameters that can be
controlled in Basic mode are:
- On/Off.
- Set-point temperature.
- Operation mode (only if this is the master thermostat).
- Fan speed.
If you need to reset the thermostat to Advanced mode, access the Advanced settings menu
and activate Advanced use mode.
20
Press and
hold
Press and
hold