ABB 6955EB-102-500 Manual De Instrucciones página 48

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 66
Start-up
• Replace all caps prior to putting into operation.
The function of built-in device 6955 EB-102-500 is software-
dependent. For programming, connect a PC to the Powernet
EIB bus line by means of the ETS 2 from Version 1.2 on-
wards or Power-Project (min. Vers. 3.0) by means of the EIB
RS 232 interface.
Allocation of the Physical Address
• Switch on the supply voltage.
• Press the programming button (Fig. 1, Pos. 3) on built-in
device 6955 EB-102-500. The red programming LED
(Fig. 1, Pos. 2) illuminates.
• The red LED extinguishes after the physical address has
been programmed.
• Note the number of the physical address on device, if
appropriate, using a non-smudge pen.
Selection/Parameterization of the Application
Please refer to the current Technical Manual for a description
of the available applications/versions and appurtenant para-
meters.
GB
Tabla de contenido
loading

Este manual también es adecuado para:

Gjb 000 6900 a1676

Tabla de contenido