6. Continue with 1 in. fittings and pipe to the
house plumbing. An optional 1 in. union (not
included) is recommended for easy connection
and disconnection. An optional shut off valve
(not included) is also recommended.
7. IMPORTANT: Air pressure in the tank
must be 2 psi lower than the "cut-in" of
the pressure switch. Pump/tank (A) has a
20/40 psi pressure switch, so tank pressure
must be set at 18 psi. Locate the air valve/
stem on the tank and check pressure with
a tire gauge (not included). If air needs to
be removed, press down on valve to bleed
air off. Use a tire pump or air compressor to
add air if needed.
PUMP ELECTRICAL CONNECTIONS
WARNING:
Always disconnect pump from electricity before
performing any work on the motor.
Under-sized wiring can cause motor failure and
even fire. Use proper wire size specified in the Wire
Size Chart.
Replace damaged or worn wiring cord immediately.
Do not kink power cable and never allow the cable
to come in contact with oil, grease, hot surfaces, or
chemicals.
The pump must be properly grounded using the
proper wire cable with ground.
CAUTION:
Protect the power cable from coming in contact with
sharp objects.
All wiring should be performed by a qualified
electrician in accordance with the National Electric
Code and local electric codes.
6
To house plumbing
1 in. union
7
Air Valve/Stem
Distance from
Motor to Meter
0-50 Ft.
50-100 Ft.
100-150 Ft.
150-200 Ft.
200-300 Ft.
Fuse Size (Amps)
(*) Not economical to run in 115 V,
use 230 V
11
Shut off valve
Tank
Tire gauge
WIRE SIZE CHART
Recommended
Copper Wire and
Fuse Sizes
Single Phase
Motors
1/2 HP
115 Volt
14
12
10
8
*
15
230 Volt
14
14
14
14
12
15