Freecooling system with 2 Way valves
EWADC12CF-XS/XL ÷ EWADC16CF-XS/XL - EWADC11CF-XR ÷ EWADC15CF-XR
EEWT = Water entering temperature probe
ELWT = Water leaving temperature probe
System change over is controlled by embedded unit controller, depending from operating conditions and unit s etpoint. Between
winter and summer operation the water side pressure drops are different, consequently the chiller water flow could be differe nt.
Evaluate that the minimum and maximum water flow, between summer and winter operation, are inside the water flow limits (see
product manual).
D-EIMAC00608-16EU - 19/234