INDICATIONS
CODE
MEANING
rhL
Low RH% function selected
rhH
High RH% function selected
The keypad is blocked
Loc
The working Set Point is blocked
- - - -
Requested function is not available
 DISPLAYS
CHAMBER TEMPERATURE
Displayed with the instrument on, during normal operation.
EVAPORATOR TEMPERATURE (with the evaporator sensor present)
Press the
button for a few seconds, then press the
select "Pb2".
Press the
button for the evaporator temperature to appear on the display.
Press
once again or do not operate to return to the chamber temperature.
CONDENSER TEMPERATURE (with the condenser sensor present)
Press the
button for a few seconds, then press the
select "Pb3".
Press the
button for the condenser temperature to appear on the display.
Press
once again or do not operate to return to the chamber temperature.
COMPRESSOR OPERATION TIMER (if present)
Press the
button for a few seconds, then press the
select "CH".
Press the
button for the compressor operation hours to appear on the
display. Press
once again or do not operate to return to the chamber
temperature.
 SETTING THE DATE AND TIME
Press the
button for a few seconds, then press the
select "rtc".
Press the
button for the following to appear on the display in sequence:
"yy", "nn", "dd", "hh" and "nn" followed by 2 numbers that correspond
respectively to the year, month, day, hour and minutes; values that can be
adjusted by acting on the
or
To exit from the procedure press
 SETTING THE SET POINT
Press the
button: the compressor LED will fl ash.
Press the
or
button within 15 seconds.
Press the
button or do not operate for the compressor LED to go off, after
which the instrument will exit from the procedure.
 ALARMS
(if present)
CODE
TYPE OF ALARM
minimum temperature alarm (HACCP alarm)
SOLUTIONS
Verify the chamber temperature
Verify the temperature associated with the alarm
AL
See the A0 +A1 + A2 parameters
CONSEQUENCES
Alarm saved
Alarm output activated with u1=3
or
or
or
(if present)
or
button.
.
maximum temperature alarm (HACCP alarm)
SOLUTIONS
Verify the chamber temperature
AH
See the A4 and A5 parameters
CONSEQUENCES
Alarm saved
Alarm output activated with u1=3
micro port input alarm (HACCP alarm)
SOLUTIONS
Verify what caused the input activation
See the i0, i1 and i4 parameters
id
CONSEQUENCES
Effect like the i0 parameter
Alarm saved with i4=1
Alarm output saved with u1=3
power failure alarm
SOLUTIONS
Verify what caused the power failure
See the AA parameter
PF
Press a button to restore the normal display
CONSEQUENCES
Alarm saved with interruption time exceeding parameter AA
Alarm output activated with u1=3
multifunction input alarm
SOLUTIONS
button to
Verify what caused the input activation
iA
See the i5 and i6 parameters
CONSEQUENCES
Effect established by the i5 parameter
Alarm output activated with u1=3
pressure switch alarm
SOLUTIONS
button to
Verify what caused the input activation
See the i5, i6, i7, i8 and i9 parameters
iSd
Switch the instrument off and on again or disconnect the
power supply
CONSEQUENCES
The regulators go off
Alarm output activated with u1=3
button to
overheating condenser alarm
SOLUTIONS
Verify the condenser temperature
COH
See the C6 parameter
CONSEQUENCES
Alarm output activated with u1=3
compressor blockage alarm
SOLUTIONS
Verify the condenser temperature
See the C7 parameter
button to
Switch the instrument off and on again: if the condenser
CSd
temperature is still > parameter C7 when it is switched on
again, disconnect the power supply and clean the condenser
CONSEQUENCES
The evaporator compressor and fan go off
Alarm output activated with u1=3
Once the cause that triggered the alarm is resolved, the instrument restores
normal operation, except for the following alarms that require:
• "PF" (power failure) - any button to be pressed;
• "iSd" (pressure switch) - the instrument to be switched off or the power supply
• "CSd" (blocked compressor) - the instrument to be switched off or the power
 ERRORS
CODE
MEANING
chamber sensor error
SOLUTIONS
Verify the type of sensor
Verify the integrity of the sensor
Verify the instrument-sensor connection
Verify the chamber temperature
Pr1
CONSEQUENCES
Compressor on or off for 10 min
Defrosting will not be activated
Alarm output activated with u1=3
The door resistors go off with u1=4
Disabling the evaporator valve with u1=5
to be disconnected
supply to be disconnected
EN - 13