Installation
1. Ensure Mains voltage cover in HWI-LV24-CE enclosure is
securely installed. Locate and lock supply breaker in the
OFF position before installing processor assembly.
Danger - Wiring with power on may result in
personal injury.
2. Install processor assembly in the enclosure: The
HomeWorks
4 Series
Processor is attached to the
®
TM
HWI-LV24-CE enclosure using four mounting keyholes
and the mounting screws provided.
The 4 Series Processor mounts
in the upper left corner of an
HWI-LV24 enclosure.
High-voltage enclosure
(shown with cover installed).
3. Set processor address. Set processor address using
the Configuration Switch. The HomeWorks Illumination
Software will prompt the programmer if any subsequent
changes to the configuration switches are required (see
Table 2). The factory installed Dimmer Hub (H4P5-H48-
CE and H4P5-H48-HRL-CE only) is already addressed to
"1".
Table 2 - Configuration Switch Functions
DIP Switch
Function
1
Boot Mode. Unless prompted by the
HomeWorks Illumination Software, this switch
should always be in the DOWN position.
2
UP = 9600 Baud,
DOWN = User selected Baud.
3-6
Processor Address. See Figure 3, below.
Example: Setting Switch #6 ON.
Down (OFF)
Up (ON)
Figure 3 - Processor Addressing
2
Figure 2 - Mounting
Diagram
TM
4. Connect to HomeWorks lighting controls. For the
H4P5-H48-CE and H4P5-H48-HRL-CE models only,
connect the communication wiring from the HomeWorks
Maestro
Dimmers to the factory installed Dimmer Hub
®
(HWI-H48-CE). See Figure 4, page 3. Connect the buses
according to the bus assignments that were made using
the HomeWorks Illumination Software. Gray and violet
connections are marked on the printed circuit board.
5. Connect Dimmer Hub links: For the H4P5-H48-CE and
H4P5-H48-HRL-CE model only, an internal harness con-
nects Link 4 to the factory installed Dimmer Hub. If addi-
tional HWI-H48-CE or HWI-Q96 boards are to be con-
trolled by the processor, the communication link to those
boards should be connected into the Link 4 terminal
block. Do not connect terminal 2 to an HWI-H48-CE or
HWI-Q96. If the H48/Q96 Link has a cable length of 15 m
(50 ft.) or more, LT-1 link terminators must be installed
across MUX and MUX (terminals 3 and 4) at both ends
of the link. Refer to HWI-H48-CE or HWI-Q96 instruc-
tions (see also Figure 5, page 4).
Note - Links 4, 5 and 6 are configurable for use
as Keypad Links, GRAFIK Eye
H48/Q96 Links. These links are configured by the
HomeWorks Illumination Software.
6. Connect Inter-processor Link (multiple processor
installations only): The Inter-processor Link is used for
communication between HomeWorks Processors.
Connect control wiring to the Inter-processor Link (Link
2), if required. Do not connect terminal 2 (see Figure 5,
page 4). If this processor is to be the first or last
processor in the daisy chain, attach one of the LT-1 link
terminators provided across the MUX and MUX
(terminals 3 and 4—see Figure 5, page 3). If LT-1
terminators are unavailable, a 1/2 W resistor between
100 and 150 Ohms may be placed across terminals 3
and 4 to provide termination.
7. Connect GRAFIK Eye / WPM links: If GRAFIK Eye
preset dimming controls or Wallbox Power Modules are
to be controlled by this processor, connect the
communication wires to Link(s) 4, 5, or 6 as configured in
the HomeWorks Illumination Software. Do not connect
terminal 2.
8. Connect Keypad links: For keypads or keypad link
devices (e.g. HWI-CCO-8) that are to be controlled by
this Processor, connect the communication wires to
Link(s) 4, 5, or 6 as configured in the HomeWorks
Illumination Software. Note: Connecting keypads or
keypad link devices to links other than Link 6 requires an
additional power supply.
9. Connect Hybrid Repeater link: For the H4P5-H48-HRL-
CE and H4P5-HRL-CE models only, connect the Hybrid
Repeater communication wires to Link 8. Note: DO NOT
connect the +15 V terminal (terminal 2) if the Hybrid
Repeater(s) will be powered by the plug-in 9 V
provided with the repeater(s).
10.Connect power. Plug the power input harness terminals
(yellow wires) from the HWI-LV24-CE enclosure onto the
power feed lugs on the 4 Series Processor. Connect plug
from adapter to Link 6 Power connector. Plug adapter
/WPM Links, or
®
adapter