IO-Link connection
The IO-Link is connected using a 5-pin connector. Connect the leads to the connector (2) on the
hybrid motor starter. The 24 V of power is supplied via A1/L+ and A2/L-. IO-Link communication
is through C/Q. The terminals labelled NC are not assigned.
®
Enable input
To start operating the motor connected to the device, the enable input must be used to enable
the device. As soon as the enable input (at terminals EN+ and EN) has a valid signal, the device
accepts control commands via the bus connection.
For non-safety related applications, enable can also be activated by bridging the terminals (EN-)
and (-) and terminals (EN+) and (+). Power interruptions ≤ 3 ms or voltage pulses ≤ 4 ms are
filtered.
Revision 1, dated 01/2021