Flare
Refrigerant
Nut
Piping
Outdoor Unit
Service
3 way Valve
Port
Outdoor Unit
Refrigerant Piping
Liquid Valve
Low Side
Pressure Gauge
Gas Valve
Manifold
2. Additional Charge
The refrigerant is pre-charged in the outdoor unit. If the piping length is less than 5m, additional charge after vacuuming is not
necessary. When the piping length is more than 5m, use the table below.
Additional Charge in Gram (Cooling Only Unit) (R410A)
Model
7m
10m 15m 20m
CCX10C
27
67
CCX15C
27
67
CCX20C
27
67
CCX25C
68
171
Additional Charge in Gram (Cooling Only Unit) (R22)
Model
7m
10m 15m 20m
CCX10C
30
75
CCX15C
30
75
CCX20C
30
75
CCX25C
76
190
3. Check Refrigerant Leak
Outdoor Unit
Liquid Valve
Gas Valve
VACUUMING AND CHARGING
Flexible Hose
4 mm
Allen
Key
Indoor Unit
High Pressure Gauge
Flexible Hose
Vacuum Pump
-
-
-
-
135
-
342
-
-
-
-
-
150
-
380
-
Refrigerant Piping
Low Side Pressure
High Pressure
Gauge
Gauge
Manifold
Flexible Hose
R410A
Refrigerant Gas Tank
1. Purging The Piping And The Indoor Unit
Except for the outdoor unit which is pre-charged with refrigerant,
the indoor unit and the refrigerant connection pipes must be
airpurged because the air containing moisture that remains in the
refrigerant cycle may cause malfunction of the compressor.
The outdoor unit is equipped by two 3 ways refrigerating
connecting valves. The suction valve is the larger one while the
small one is the liquid valve. Both valves are supplied with service
port valve for connection to a manometer.
• Remove the caps from the valve and the service port.
• Connect the center of the charging gauge to the vacuum pump.
• Connect the charging gauge to the service port of the 3-way
valve.
• Start the vacuum pump. Check the low pressure manifold gauge
until it indicates 0.9 bar. The evacuation time varies with each
vacuum pump capacity but generally in half an hour.
• Close the manifold valve and stop the vacuum pump.
• On the outdoor unit, open the suction and liquid valve (anti
clockwise) with 4mm key for hexagon sacked screw.
• The air conditioner unit is ready for start.
• If the reading is close to 0, the refrigerant circuit must be
evacuated (by vacuum pump) and charged again.
Additional Charge in Gram (Heat Pump Unit) (R410A)
Model
CCX10CR
CCX15CR
CCX20CR
CCX25CR
Additional Charge in Gram (Heat Pump Unit) (R22)
Model
CCX10CR
CCX15CR
CCX20CR
CCX25CR
Indoor Unit
Check with refrigerant detector whether there is a
leak on the flare type connection of the indoor unit
and outdoor unit.
Hints: After operation for sometimes, check if
6
7m
10m 15m 20m
36
90
-
-
36
90
-
-
45
112
225
-
90
225
450
-
7m
10m 15m 20m
40
100
-
-
40
100
-
-
50
125
250
-
100
250
500
-
there is oil traces, there is a leak.