11.8.5 Assigning and setting the alarm relay
Main menu > Setup
Submenu 1
Alarm relay
The following faults are output as alarm messages,
and the alarm relay switches automatically:
•
battery backup fault
•
open circuit current output.
If the alarm state is removed, the relay immediately
falls back automatically (no delay).
In addition, this submenu contains the following
settings for the alarm relay:
•
Selection of whether the alarm relay operates as
N.C. (fail safe) or N.O. contact
•
Confirmation of alarm messages.
In addition, for each sensor certain events can be
output to the alarm relay:
•
- exceeding of limit value 1
•
- exceeding of limit value 2
•
- fault during sensor test.
An alarm delay can be set in the relevant
Note
sensor menu in the main menu.
Submenu 2
Fail safe
Confirmation
Sensor 1
Sensor 2
Submenu 3
On (N.C.)
Off (N.O.)
Yes
No
Limit value 1 (S1)
Limit value 2 (S1)
Test sensor
Limit value 1 (S2)
Limit value 2 (S2)
Test sensor
Submenu 4
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
37