7. Faults
Faults
No output signal
EN
Deviating zero point signal
Deviating zero point signal
Constant output signal upon change in
pressure
Signal span varies
Signal span varies/inaccurate
Signal span drops/too small
If complaint is unjustified, we will charge you the complaint processing fees.
14
Causes
Cable break
Overload safety exceeded
Too high/low working temperature
Mechanical overload caused by overpres-
sure
EMC interference sources in the environ-
ment; for example, frequency converter
Too high/low working temperature
Mechanical overload caused by overpres-
sure
WIKA operating instructions pressure transmitter, model S-10
Measures
Check the continuity
Observe the permissible overload safety
Observe the permissible temperatures
Replace instrument; if it fails repeatedly,
contact the manufacturer
Shield instrument; cable shield; remove
source of interference
Observe the permissible temperatures
Replace instrument; if it fails repeatedly,
contact the manufacturer