Tripp-Lite SmartPro AGSM7715 El Manual Del Propietario página 8

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Optional Connections
External Battery Connection
3
Your UPS contains a robust internal battery system.
External batteries are needed only to extend
runtime. Use only Tripp Lite external battery packs
with overcurrent protection. Adding external
batteries will increase recharge time as well as
runtime. Installation should be performed by
qualified service personnel only. Refer to the battery
pack owner's manual for complete installation
instructions.
Illustration
3
External Battery Connector
the battery pack cable. Complete installation
instructions for your battery pack appear in the
battery pack owner's manual. Make sure cables are
fully inserted into their connectors. Small sparks
may result during battery connection. This is
normal. Do not connect or disconnect battery
packs when the UPS is running on battery power.
Your UPS supports the following battery packs
available from Tripp Lite. Contact Tripp Lite
Customer Support at 773.869.1234 for the
appropriate Tripp Lite battery pack to connect.
48V Battery Packs:
BP48V24-2U, 18Ah, (Limit 1)
BP48V60RT-3U, 42Ah (Unlimited)
BP48V48RT4U, 42Ah (Unlimited)
When installing your UPS with External Batteries,
be sure to connect the ground strap between the
external battery packs to the metal enclosure of the
UPS before connecting to the two-conductor
external battery pack cables.
Follow installation directions in accordance with the
External Battery Pack Owner's Manual, using the
ground strap included with the external battery
packs. Do not connect or disconnect battery packs
when the UPS is running on battery power.
18-11-091-932968.indb 8
shows the location of your UPS
, where you will insert
A
A
3
8
12/12/2018 9:58:51 AM
Tabla de contenido
loading

Tabla de contenido