NOTE
The light band has to be positioned parallel to the conveyor belt.
It is important to ensure that the light band is positioned directly above the conveyor belt,
otherwise small objects may not be detected.
4
Tip:
1
Fine adjustment of the light band: Fold white A4 sheet twice. The light band must be
visible on both conveyor belt edges evenly in their entire height on the white paper.
The conveyor belt must not be in the light band. The light band must be aligned in
parallel without any gap over the conveyor belt. It should be noted that the setting of
the light band is minimal can change if the screws are tightened on the bracket.
2
Note the triple structure of the reflector:
correct:
3
Control of the setting: Switch on conveyor belt. In "idling mode" (conveyor belt moves
without material to be conveyed), the sensor must not switch. Switch on conveyor
belt. Place the goods in succession on the conveyor belt edges and in the middle on
the belt to check the reliable detection in three places.
4
There is no feedback on the signal strength light bar for correct parallel installation near
the conveyor bottom.
2
Sensing range
Adjust the distance between the sensor and the reflector according to the corresponding
diagram
see figure 7, page
not correct:
12.
COMMISSIONING
4
4
7