2.7
Gas pressure - output
Pressure measured at the coupling (5)(Fig. 3) with combustion
chamber at 0 mbar and burner in 2nd stage operation.
2.8
Combustion chamber pressure
The combustion chamber pressure is the same as for natural
gas.
For pressure levels different from those indicated
above, please contact the Technical Office.
WARNING
2.9
Pressure loss diagrams
The gas trains for LPG operation (G31= 24.44 kWh/Sm3) are the
same as those used for natural gas.
The diagrams report the minimum pressure required before the
filter, to have the maximum output with combustion chamber
pressure at 0 mbar.
For the max pressure allowed by the gas train approval, and for
the diagram references see the burner instruction, the gas train
instruction or the instruction manual burner combined with the
gas train.
2915572
LPG kit
If the combustion chamber is pressurized, the required gas-pres-
sure is that shown on the diagram plus the pressurization value
Output
kW
1280
1392
1504
1617
1729
1841
1953
2066
2178
2290
4
GB
.
20144798
Fig. 4
p (mbar)
G 31
11.4
12.8
14.4
16.3
18.4
20.7
23.3
26.1
29.1
32.4
Tab. C