1. Deactivate the control interface (device control with
control panel: HMI = on).
2. Select the drive type and, if necessary, adapt the
parametrization to the axis.
3. Set the parameters for the reference run:
4. Carry out reference run.
After a successful reference run:
5. Teach axis zero point and working range:
6. Enter position sets (target position, positioning mode,
positioning speed, acceleration).
7. Check the positioning behaviour of the axis, reference
coordinates and working range (test run).
8. If necessary, optimize the position sets, reference
coordinates and working range.
9. Deactivate the control interface (device control with
control panel HMI = off ).
10. Protect settings against unauthorized access with a
password.
Festo P.BE−K−SFC−DC−IO 0503NH English
Reference run method (to stop or reference switch)
Search speed to reference point
Positioning speed to axis zero point
With referencing method Fixed stop ...":
Teach axis zero point
Offset of the axis zero point to the reference point
Positive and negative software end positions
0 if necessary.