IAQ Monitor/ English
Ventilation Formula
CFM/P(inch/minute/person)
CFM/P = 10600/(Cs-Co)
Cs = CO2 read value, Co = CO2 outdoor read value.
L/P/S(liter/second/person)
L/P/S=(CFM/P)*28.32/60
Software Installation
The package contains: CD and USB cable
Systems requirement : XP/ Windosw7/ Windows 8.1/
1. Insert the CD into the PC to install the desktop program:
EN-10
Windows10
2016-10-17 V001