Configuration - Festo CPV Instrucciones Para El Usuario

Ocultar thumbs Ver también para CPV:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 31
3

Configuration

Caution
The CPV Direct contains electronically sensitive compo
nents. The CPV Direct will be damaged if you touch the
contact surfaces of the plug connectors or if you do not
observe the regulations for handling electrostatically
sensitive components.
Proceed with the configuration as follows:
1. Switch off the power supply.
2. Remove the switch cover.
3. Set the following with the DIL switches: the baud rate,
station number, tool change configuration.
4. Switch on the power supply.
5. If modules or valve terminals are connected to the
CPI extension connection: Carry out automatic
recognition (see section 5.2, not necessary in tool
change configuration).
6. Refit the switch cover.
7. If the CP Direct is the first or last slave in a field bus
segment, a terminating resistor must be fitted
between the field bus cables (120 , 0.25 W).
Warning
S Check the measures for putting the system into a
safe state in the event of an EMERGENCY STOP.
Further information: Manual P.BE−CP−CO3−...
Festo CPV...−GE−CO3−8 0709NH English
21
Tabla de contenido
loading

Tabla de contenido