The use of PELV circuits ensures protection from electric shock (protection from
direct and indirect contact) in accordance with IEC/EN 60204-1 (Electrical equip-
ment of machines, General requirements).
Note
Incorrect handling can cause damage to the electronics modules.
S Switch off the supply voltage before conducting any mounting or installation
work.
S Only switch on the electrical supply voltage when the product has been fully
assembled and all of the installation work is complete.
S Electronic modules include electrostatically sensitive devices. Therefore, do
not touch any components. Observe the handling specifications for electro-
statically sensitive devices.

Setting the PROFIsafe address

To allow communication via PROFIsafe, the correct PROFIsafe address must be set
with binary coding on the shut-off module via a 10-position DIL switch. Permissible
are the PROFIsafe addresses in the range from 1 to 1023. The DIL switch is located
directly on the electronics module and can be adjusted when the connection block
is removed. The following image shows the DIL switch with addressing examples.
10-position DIL switch
Fig. 5: 10-position DIL switch of the output module CPX-FVDA-P
34
Addressing example
2 + 64 + 512 = 578
1
2
4
8
16
32
64
128
256
512
Festo CPX-FVDA-P-Z6 1303a English