Technical Data; Commissioning The Device; Operations Prior To Installation - Madas M16/RM N.A. EEX Manual Del Usuario

Electroválvula con rearme manual normalmente abierta para gas
Ocultar thumbs Ver también para M16/RM N.A. EEX:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

2.0 - TECHNICAL DATA

• Use
• Ambient temperature (TS)
• Power voltages (see table 2)
• Power supply tolerance
• Electric wiring
• Absorbed power
• Maximum operating pressure
• Closing time
• Protection rating
• Coil protection mode
• Mechanical resistance
• Rp threaded connections
• Flanged connections to be coupled
with PN 16 flanges
• NPT threaded or ANSI flanged connections : on request
• In compliance with
* Only single-phase, the device does not work if powered with three-phase
** DN 25 with swivel flanges.

3.0 - COMMISSIONING THE DEVICE

3.1 - OPERATIONS PRIOR TO INSTALLATION

• It is necessary to close the gas upstream of the valve prior to installation;
• Make sure that the line pressure DOES NOT EXCEED the maximum pressure declared on the product label;
• Any protective caps (if any) must be removed prior to installation;
• Valve pipes and insides must be clear of any foreign bodies;
If the device is threaded:
• make sure that the pipe thread is not too long, to prevent damaging the body of the device when screwing it on;
If the device is flanged:
• make sure the inlet and outlet counter-flanges are perfectly coaxial and parallel in order to prevent unnecessary
mechanical stress to the body. Also calculate the space to insert the seal gasket;
• With regard to tightening operations, equip yourself with one or two calibrated torque wrenches or other controlled
locking tools;
• In accordance with EN 161 a suitable filter must be installed upstream of a gas closing safety device;
• With outdoor installation, it is advisable to provide a protective roof to prevent rain from damaging the electrical parts of
the device.
• Prior to carrying out any electrical wiring operations, make sure that the main voltage matches the supply voltage indicated
on the product label;
M16/RM N.A. EEX
: non-aggressive gases of the three families (dry gases)
: -20 ÷ +50 °C
: 12 Vdc - 24 Vdc - 24 V/50-60 Hz - 110 V/50-60 Hz - 220-240 V/50-60 Hz*
: -15% ... +10%
: electric cable l=3 metres with wire terminals
: see table 2
: 6 bar
: < 1 s
: IP65
: see table 2
: Group 2 (according to EN 13611)
: (DN 20 - DN 25 - DN 32 - DN 40 - DN 50) according to EN 10226
: (DN 25** - DN 32 - DN 40 - DN 50) ISO 7005 / EN 1092-1
: ATEX Directive 2014/34/EU - PED Directive 2014/68/EU
EMC Directive 2014/30/EU - LVD Directive 2014/35/EU
RoHS II Directive 2011/65/EU
10
Madas Technical Manual - 3|3.3b - REV. 0 of 10
voltage.
Sep 2019
th