Safety devices

Photocells
Confi gure the CX contact (NC), input for safety devices such as
photocells.
When programming the functions, the (F2) CX input can be set
to:
- C1reopening during closing. When the gate is closing, opening
the contact triggers the inversion of movement until the gate is
fully open again;
- C2close back up during opening. When the gate is opening,
opening the contact triggers the inversion of movement until the
gate is completely closed.
- C3partial stop. Stopping of the gate, if it is moving, with
consequent automatic closing (if the automatic closing function
has been entered);
- C4obstruction wait. Gate stops, if it is moving, and once the
obstruction is removed, it resumes its movement.
 If unused, the CX contact should be deactivated during
programming.
 If you wish to add a second pair of photocells, make the
electrical connections by using input CY as show in the fi gure
and set the function on F3.