Cable Type And Minimum Thicknesses - Motostar MP100 Manual De Instalación Y De Uso

Automatización utomatización para puertas peatonales uertas peatonales batientes
Ocultar thumbs Ver también para MP100:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 123

Cable type and minimum thicknesses

Connection
Control board power supply 230 V AC (1P+N)
24 V DC gearmotor
Electric lock
Flashing light
Command and control devices
TX Photocells
RX photocells
 When operating at 230 V and outdoors, use H05RN-F-type cables that are 60245 IEC 57 (IEC) compliant; whereas indoors, use
H05VV-F-type cables that are 60227 IEC 53 (IEC) compliant. For power supplies up to 48 V, you can use FROR 20-22 II-type cables
that comply with EN 50267-2-1 (CEI).
 If cable lengths differ from those specified in the table, establish the cable sections depending on the actual power draw of the
connected devices and according to the provisions of regulation CEI EN 60204-1.
 For multiple, sequential loads along the same line, the dimensions on the table need to be recalculated according to the actual
power draw and distances. For connecting products that are not contemplated in this manual, see the literature accompanying said
products
cable length
< 20 m
20 < 30 m
2
2 x 1.5 mm
2 x 2.5 mm
2
3 x 1.5 mm
3 x 2.5 mm
2
2 x 0.5 mm
2
2 x 0.5 mm
2
2 x 0.5 mm
2
2 x 0.5 mm
2
4 x 0.5 mm
2
2
Tabla de contenido
loading

Tabla de contenido